 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 03 - THERE ARE TWO EXISTING BATHROOMS WITH
 DOORS SHOWN AS OPENING INTO THE REQUIRED EGRESS WIDTH
 OF THE CORRIDOR.
  
 THERE ARE NO DOOR SCHEDULES SHOWING HARDWARE OR HINGE
 TYPES.
  
 PER NFPA 101 CH 7. MEANS OF EGRESS
  
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR
 LEAF IS FULLY OPEN.
  
 PLEASE REVIEW AND CORRECT THE ONE DOOR SWING OR 180
 HINGE AND THE OTHER CHANGE THE SWING OR SHOW DIMENSION
 OF SPACE BETWEN WALL AND DOOR THAT MEETS THE
 REQUIREMENT.
  
  
  
 2) SHEET A 05 - THERE IS AN INDICATION OF A
 RANGE/STOVE/VENT WITHIN THE KITCHEN.
  
 IS THIS KITCHEN RANGE/STOVE/VENT FUNCTION OR JUST FOR
 SHOW?
  
 PLEASE PROVIDE A NOTE OF NON-FUNCTIONAL OR DETAILS OF
 FUNCTION AS APPLICABLE.
  
  
  
 3) SHEETS A 03 & 07 - THERE ARE NO INDICATIONS OF FIRE
 SPRINKLER AND/OR FIRE ALARM WORK.
  
 ALL WORK ON THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS
 SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
  
 ALL WORK ON THESE SYSTEMS SHALL BE DONE BY CERTIFIED FA
 & FS CONTRACTORS.
  
 PLEASE ENSURE COMPLIANCE AND PROVIDE AN APPLICABLE NOTE
 OF ACKNOWLEDGEMENT.
  
  
  
 4) THERE ARE NO INDICATIONS OF A DOOR SCHEDULE FOR ANY
 OFHTE NEW NOR EXISTING DOORS, INCLUDING ALL HARDWARE,
 CLOSERS, ETC.
  
 PER NFPA 101, CH 38 NEW BUSINESS OCCUPANCIES
  
 38.2.2 MEANS OF EGRESS COMPONENTS.
 38.2.2.1 GENERAL. MEANS OF EGRESS COMPONENTS SHALL BE
 LIMITED
 TO THE TYPES DESCRIBED IN 38.2.2.2 THROUGH 38.2.2.12.
 38.2.2.2 DOORS.
 38.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 38.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED
 ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS.
  
 PLEASE REVIEW AND PROVIDE A DOOR SCHEDULE.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  