Date |
Text |
2019-05-21 15:26:59 | 5/21/19 |
| |
| THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) SHEET A 03 - THERE ARE TWO EXISTING BATHROOMS WITH |
| DOORS SHOWN AS OPENING INTO THE REQUIRED EGRESS WIDTH |
| OF THE CORRIDOR. |
| |
| THERE ARE NO DOOR SCHEDULES SHOWING HARDWARE OR HINGE |
| TYPES. |
| |
| PER NFPA 101 CH 7. MEANS OF EGRESS |
| |
| 7.2.1.4.3 DOOR LEAF ENCROACHMENT |
| 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE |
| REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, |
| OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT |
| MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A |
| CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, |
| UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: |
| (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| EXISTING BUILDING. |
| (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS |
| PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED |
| WIDTH OF THE STAIR LANDING WHEN THE DOOR |
| LEAF IS FULLY OPEN. |
| |
| PLEASE REVIEW AND CORRECT THE ONE DOOR SWING OR 180 |
| HINGE AND THE OTHER CHANGE THE SWING OR SHOW DIMENSION |
| OF SPACE BETWEN WALL AND DOOR THAT MEETS THE |
| REQUIREMENT. |
| |
| |
| |
| 2) SHEET A 05 - THERE IS AN INDICATION OF A |
| RANGE/STOVE/VENT WITHIN THE KITCHEN. |
| |
| IS THIS KITCHEN RANGE/STOVE/VENT FUNCTION OR JUST FOR |
| SHOW? |
| |
| PLEASE PROVIDE A NOTE OF NON-FUNCTIONAL OR DETAILS OF |
| FUNCTION AS APPLICABLE. |
| |
| |
| |
| 3) SHEETS A 03 & 07 - THERE ARE NO INDICATIONS OF FIRE |
| SPRINKLER AND/OR FIRE ALARM WORK. |
| |
| ALL WORK ON THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS |
| SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS. |
| |
| ALL WORK ON THESE SYSTEMS SHALL BE DONE BY CERTIFIED FA |
| & FS CONTRACTORS. |
| |
| PLEASE ENSURE COMPLIANCE AND PROVIDE AN APPLICABLE NOTE |
| OF ACKNOWLEDGEMENT. |
| |
| |
| |
| 4) THERE ARE NO INDICATIONS OF A DOOR SCHEDULE FOR ANY |
| OFHTE NEW NOR EXISTING DOORS, INCLUDING ALL HARDWARE, |
| CLOSERS, ETC. |
| |
| PER NFPA 101, CH 38 NEW BUSINESS OCCUPANCIES |
| |
| 38.2.2 MEANS OF EGRESS COMPONENTS. |
| 38.2.2.1 GENERAL. MEANS OF EGRESS COMPONENTS SHALL BE |
| LIMITED |
| TO THE TYPES DESCRIBED IN 38.2.2.2 THROUGH 38.2.2.12. |
| 38.2.2.2 DOORS. |
| 38.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| PERMITTED. |
| 38.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE |
| PERMITTED |
| ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS. |
| |
| PLEASE REVIEW AND PROVIDE A DOOR SCHEDULE. |
| |
| |
| |
| 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |