Plan Review Notes
Plan Review Notes For Permit 19050604
Permit Number 19050604
Review Stop E
Sequence Number 1
Notes
Date Text
2019-05-31 15:07:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 2. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
 3. RISER DIAGRAM SHOWS A THREE PHASE FEEDER BEING
 EXTENDED TO PANEL B. HOWEVER, THE PANEL SCHEDULE FOR
 PANEL B SHOWS IT AS A SINGLE PHASE PANEL. WHICH IS IT?
 PROVIDE CLARIFICATION AND CORRECTIONS AS NEEDED. WPB
 FBC 107.2.1; NEC 408.4, 408.30, 408.36
 4. RISER DIAGRAM SHOWS PANEL A AND PANEL M BEING FED
 FROM THE SAME METER CAN, BUT ONE OF THESE PANELS IS
 SHOWN AS THREE PHASE AND ONE OF THEM IS SHOWN AS SINGLE
 PHASE. IS THIS ACCURATE? PROVIDE CLARIFICATION AND
 CORRECTIONS AS NEEDED. PROVIDE RATING OF EXISTING METER
 CAN AND LOAD CALCULATION TO CONFIRM CAPACITY IS
 ADEQUATE. WPB FBC 107.2.1; NEC 220, 408.30, 408.36
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  