2019-06-04 10:28:58 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19050604 |
| ADD: 1217 S FLAGLER DR. 3RD FLOOR |
| CONT: NICK RAICH BUILDING CORP. |
| TEL: 561-659-9347 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. JUNE 04/ 2019 |
| ACTION: DENIED |
| |
| 1) THIS BUILDING IS LOCATED IN A FLOOD ZONE. ARTICLE |
| XVII ORDINANCES ARTICLE XVII FLOOD PREVENTION & CONTROL |
| FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION |
| 94-546. STRUCTURE IS LOCATED IN AN "AE" FLOOD ZONE. A |
| FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE |
| REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE |
| AFTER OCT. 11/ 2017 AN ADDITIONAL ONE FOOT OF FREE |
| BOARD WILL BE REQUIRED OR (2) FEET ABOVE BASE FLOOD. |
| BASE FLOOD ELEVATION (BFE) 6? NAVD88 OR FIS 5.7?. THE |
| COMBINED VALUE OF THIS BUILDING AND LOT ACCORDING TO |
| THE PALM BEACH COUNTY PROPERTY APPRAISERS OFFICE IS |
| $1,300,000.00 DOLLARS. |
| |
| SUBSTANIAL IMPROVEMENT. SECTION 94-546 PROVISIONS FOR |
| FLOOD HAZARD REDUCTION. (A)(3) ANY ALTERATION, REPAIR, |
| RECONSTRUCTION, OR IMPROVEMENTS TO A PROPERTY WHICH THE |
| CUMULATIVE COST FOR ANY FIVE YEAR PERIOD EQUALS OR |
| EXCEEDS 50 % OF THE BUILDING VALUE AT THE COMMENCEMENT |
| OF THE FIVE YEAR PERIOD SHALL MEET THE REQUIREMENTS OF |
| NEW CONSTRUCTION AS CONTAINED IN THIS ARTICLE. |
| TO DETERMINE IF THE SUBSTANTIAL IMPROVEMENT VALUE FOR |
| THIS PROJECT HAS BEEN MET WE CANNOT DETERMINE THIS |
| SINCE IN THIS CASE THE PALM BEACH COUNTY PROPERTY |
| APPRAISERS OFFICE DOES NOT HAVE THE VALUE FOR THE |
| BUILDING BROKEN OUT OF THE OVERALL VALUE OF THE |
| ASSESSED PROPERTY. THE OWNER OR TENANT OF THE BUILDING |
| WILL NEED TO PROVIDE AN ASSESSED VALUE FOR THE BUILDING |
| ITSELF. |
| |
| THE PROPOSED IMPROVEMENT OVER THE LAST 5 YEARS, |
| INCLUDING THE CURRENT PROPOSED IMPROVEMENTS |
| ($413,740.00) APPEARS TO BE A SUBSTANTIAL IMPROVEMENT |
| BASED ON PROPERTY APPRAISER VALUATION FOR THE STRUCTURE |
| & LAND VALUE ($1,300,000.00 DALLORS IN VALUE). IF THIS |
| IS A SUBSTANTIAL IMPROVEMENT, THE STRUCTURE IS TO BE |
| BROUGHT INTO COMPLIANCE (BFE 6.0' + 2.0?) NAVD88 FOR |
| THE LOWEST FINISHED FLOOR, & ALL MECHANICAL EQUIPMENT). |
| APPLICANT MAY PROVIDE DOCUMENTATION FOR VALUATION OTHER |
| THAN PROPERTY APPRAISER; PLEASE SEE FEMA TECHNICAL |
| BULLETIN 758, SECTION 4.5: |
| HTTPS://WWW.FEMA.GOV/MEDIA-LIBRARY-DATA/20130726-1734-2 |
| 5045-2915/P_758_COMPLETE_R3.PDF |
| |
| 2) THE TITLE BLOCK IS CONFUSING AS TO THE LOCATION OF |
| WORK TO BE ACCOMPLISHED UNDER THIS PERMIT. AT 1ST |
| GLANCE THE COVERSHEET, A.01 IT WOULD APPEAR ALL WORK ON |
| ALL 8 ARCHITECTURAL SHEETS WOULD BE ON THE 3RD FLOOR. |
| ON SHEETS A.02-A0.4 THESE SHEETS STILL SAY SALES OFFICE |
| 3RD FLOOR AS WELL AS 2ND FLOOR PLAN. (4) SETS OF PLANS |
| WERE BROUGHT IN MAKING IT MORE CONFUSING ALL PLANS |
| LABELED THE SAME WAY FOR THE 2 PERMITS THE 2ND FLOOR & |
| 3RD FLOOR. PLEASE CORRECT THE TITLE BLOCK FOR THE COVER |
| SHEET TO INCLUDE THE 2ND FLOOR AND AS TO WHERE THE WORK |
| IS GOING TO BE COMPLETED FOR THE 2ND FLOOR FOR SHEETS |
| A.02-A0.4, NO REFERENCE TO THE 3RD FLOOR PLEASE. |
| 2017 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED. |
| |
| 3) SHEET A.05 SHOWS A CONFERENCE ROOM WITH GLASS WALL |
| AND DOOR SYSTEM. THERE IS NO MENTION IN THE PLANS TO |
| THE TYPE OF GLAZING IN EITHER THE DOOR OR GLASS WALL |
| SYSTEM. PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B |
| SECTIONS: |
| 2406.4 HAZARDOUS LOCATIONS. THE LOCATIONS SPECIFIED IN |
| SECTIONS 2406.4.1 THROUGH 2406.4.7 SHALL BE CONSIDERED |
| SPECIFIC HAZARDOUS LOCATIONS REQUIRING SAFETY GLAZING |
| MATERIALS. |
| 2406.4.2 GLAZING ADJACENT TO DOORS. GLAZING IN AN |
| INDIVIDUAL FIXED OR OPERABLE PANEL ADJACENT TO A DOOR |
| WHERE THE NEAREST VERTICAL EDGE OF THE GLAZING IS |
| WITHIN A 24-INCH (610 MM) ARC OF EITHER VERTICAL EDGE |
| OF THE DOOR IN A CLOSED POSITION AND WHERE THE BOTTOM |
| EXPOSED EDGE OF THE GLAZING IS LESS THAN 60 INCHES |
| (1524 MM) ABOVE THE WALKING SURFACE SHALL BE CONSIDERED |
| A HAZARDOUS LOCATION. |
| |
| 4) PLEASE REVIEW THE PLUMBING PLAN REVIEW COMMENTS FOR |
| SHEET A.08 FOR ACCESSIBILITY. |
| |
| 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |