2019-07-29 11:29:501) SHT. A-2 - THE GRAB BAR REINFORCING DETAIL FOR THE
 SHOWER SHALL COMPLY WITH THE FAIR HOUSING ACT GUIDLINES
 FIGURE #5. THE BACKING SHALL BE LOCATED 32 INCHES
 MAXIMUM TO THE BOTTOM OF THE BACKING. SHOW THAT THE 32
 INCHES IS MAXIMUM ON THE PLANS.
 2) THE WIDTH OF THE BACKING SHALL BE A MAXIMUM OF 6
 INCHES PER THE FHA GUIDELINES FIGURE #5, NOT 18 INCHES
 AS SHOWN ON THE PLANS. THE DETAIL NOTES A 2 X 6 METAL
 TRACK PIECE ALSO. CLARIFY.
 3) THE MAXIMUM CABINET HEIGHT FOR A SPECIFICATION TYPE
 "B" BATHROOM IS 34 INCHES PER THE FHA GUIDELINES. THE
 MASTER BATH ELEVATION DETAILS #4 & #5 ON SHT. A-3 SHOWS
 36 INCHES TO THE TOP OF THE VANITY.
 4) SHT. A-1 - NOTE # 9 STATES AN EXISTING TUB IS TO BE
 REMOVED AND A NEW TUB CONNECTED TO EXISTING PLUMBING
 YET SHEETS A-2 & P-1 SHOW A NEW SHOWER. CLARIFY.
 5) THE REINFORCEMENT DETAIL FOR THE GRAB BARS IN THE
 SHOWER ON SHT. A-2 SHALL BE LOCATED ON BOTH SIDE WALLS
 AND THE BACK WALL BUT IS ONLY SHOWN ON THE BACK WALL ON
 THE DETAIL. CLARIFY.
 6) INDICATE THE GAUGE OF THE METAL TO BE USED FOR THE
 REINFORCEMENT FOR THE SHOWER GRAB BARS. THE METAL SHALL
 BE ABLE TO SUPPORT A LOAD OF 250 LBF.
 7) CLARIFY THE DISTANCE BETWEEN THE WALL AND THE
 KITCHEN CORNER COUNTER. THE WIDTH SHALL BE 40 INCHES
 CLEAR YET THE DIMENSION LINE ON THE PLAN APPEARS TO
 ENCROACH INTO THE REFRIGERATOR AND POSSIBLY THE STOVE.
 REVISE THE DIMENSION LINE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  