2019-07-29 11:29:50 | 1) SHT. A-2 - THE GRAB BAR REINFORCING DETAIL FOR THE |
| SHOWER SHALL COMPLY WITH THE FAIR HOUSING ACT GUIDLINES |
| FIGURE #5. THE BACKING SHALL BE LOCATED 32 INCHES |
| MAXIMUM TO THE BOTTOM OF THE BACKING. SHOW THAT THE 32 |
| INCHES IS MAXIMUM ON THE PLANS. |
| 2) THE WIDTH OF THE BACKING SHALL BE A MAXIMUM OF 6 |
| INCHES PER THE FHA GUIDELINES FIGURE #5, NOT 18 INCHES |
| AS SHOWN ON THE PLANS. THE DETAIL NOTES A 2 X 6 METAL |
| TRACK PIECE ALSO. CLARIFY. |
| 3) THE MAXIMUM CABINET HEIGHT FOR A SPECIFICATION TYPE |
| "B" BATHROOM IS 34 INCHES PER THE FHA GUIDELINES. THE |
| MASTER BATH ELEVATION DETAILS #4 & #5 ON SHT. A-3 SHOWS |
| 36 INCHES TO THE TOP OF THE VANITY. |
| 4) SHT. A-1 - NOTE # 9 STATES AN EXISTING TUB IS TO BE |
| REMOVED AND A NEW TUB CONNECTED TO EXISTING PLUMBING |
| YET SHEETS A-2 & P-1 SHOW A NEW SHOWER. CLARIFY. |
| 5) THE REINFORCEMENT DETAIL FOR THE GRAB BARS IN THE |
| SHOWER ON SHT. A-2 SHALL BE LOCATED ON BOTH SIDE WALLS |
| AND THE BACK WALL BUT IS ONLY SHOWN ON THE BACK WALL ON |
| THE DETAIL. CLARIFY. |
| 6) INDICATE THE GAUGE OF THE METAL TO BE USED FOR THE |
| REINFORCEMENT FOR THE SHOWER GRAB BARS. THE METAL SHALL |
| BE ABLE TO SUPPORT A LOAD OF 250 LBF. |
| 7) CLARIFY THE DISTANCE BETWEEN THE WALL AND THE |
| KITCHEN CORNER COUNTER. THE WIDTH SHALL BE 40 INCHES |
| CLEAR YET THE DIMENSION LINE ON THE PLAN APPEARS TO |
| ENCROACH INTO THE REFRIGERATOR AND POSSIBLY THE STOVE. |
| REVISE THE DIMENSION LINE. |
| |