Plan Review Notes
Plan Review Notes For Permit 19050592
Permit Number 19050592
Review Stop P
Sequence Number 1
Notes
Date Text
2019-05-16 10:08:00PLUMBING 1ST REVIEW**DENIED** BUILDING WAS CONSTRUCTED
 IN 2006 UNDER THE FAIR HOUSING ACT** ALL CODE
 REFERENCES ARE FROM THE FAIR HOUSING DESIGN MANUAL
 EXCEPT COMMENT #6 WHICH COMES FROM FBC PLUMBING.
  
 1) PROVIDE WHAT DESIGN UNDER THE FAIR HOUSING ACT (FHA)
 YOUR BATHROOM IS DESIGNED FROM, PROVIDE EXISTING GUEST
 BATHROOM DESIGN SPEC. NOTE IF EXISTING IS SPEC A THEN
 BOTH BATHROOM SHALL BE REQUIRED TO BE SPEC A DESIGN.FBC
 107.3.5
  
 2) PROVIDE CLEAR FLOOR SPACE FOR ALL FIXTURES AS
 REQUIRED BY FHA TO INCLUDE EXISTING TO ENSURE YOUR NEW
 DESIGN COMPLIES WITH FHA 7.39. FBC 107.2.1
  
 3) PROVIDE DETAIL OF SHOWER GRAB BAR BACKING TO BE
 INSTALLED. NOTE GRAB BARS THEM SELF ARE NOT REQUIRED TO
 BE INSTALLED JUST THE ABILITY FOR THE UNIT TO BE
 ADAPTABLE. FHA 6.3, 6.12
  
 4) PROVIDE CABINET HEIGHT DETAIL FOR BOTH BATHROOM SINK
 AND KITCHEN SINK SHOWING THEY COMPLY. MAX 34" BATHROOM,
 MAX 36" KITCHEN. FHA 7.52, 7.15
  
 5) PROVIDE MEASUREMENT ON PLAN BETWEEN WALL AND KITCHEN
 COUNTER CORNER SHOWING MIN CLEARANCE OF 40" IS PROVIDE
 FOR ACCESSIBILITY INTO THE KITCHEN. FHA 7.7
  
 6) PROVIDE LOCATION OR NOTE ON PLAN THAT THE SHUT OFF
 VALVES FOR THE WASHING MACHINE SHALL BE ACCESSIBLE TO
 COMPLY WITH FBC-P 606.3
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR