2019-06-05 06:14:44ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE UL OR OTHER NRTL LISTINGS FOR ALL PROPOSED
 EQUIPMENT. PPC'S, ANTENNAS, CABINETS, "STEALTH
 ENCLOSURES" ETC. NEC 90.7, 110.2, 110.3B FBC 107.2.1
  
 2. PROVIDE LOAD CALCULATION OF EXISING 3000AMP SERVICE
 TO INCLUDE ALL LOADS, EXISING AND NEW. LOAD STUDY
 PROVIDED IS 1.5 YEARS OLD. FBC 107.2.1 NEC 220.
  
 3. NO CONDUCTOR SIZES PROVIDED TO FEED NEW METER BANK
 ENCLOSURE? NEW METER BANK WILL TIE INTO EXISITING? MORE
 INFORMATION REQUIRED. FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE