Plan Review Notes
Plan Review Notes For Permit 19050466
Permit Number 19050466
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-05-14 11:33:12THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE IS INSUFFICIENT DETAIL PROVIDE TO MAKE A
 DETERMINATION OF CODE AND LIFE SAFETY COMPLIANCE.
  
  
  
 2) THERE ARE NO DIMESNION INDICATED ON ANY LENGTH OF
 PIPE.
  
 6.6.3 PIPING FOR FUEL TANKS, OTHER THAN ENGINE-MOUNTED
 TANKS, SHALL BE IN ACCORDANCE WITH THE PROVISIONS OF
 6.6.3.1
 THROUGH 6.6.3.3, EXCEPT AS PROVIDED FOR IN 6.6.3.4.
 6.6.3.1 PIPING FOR FUEL TANKS SHALL MEET THE APPLICABLE
 REQUIREMENTS
 OF CHAPTERS 21 AND 27 OF NFPA 30, FLAMMABLE AND
 COMBUSTIBLE LIQUIDS CODE.
  
  
 3) IT APPEARS THAT THE FILL PIPE IS INSTALLED ALONG
 INTERIOR WALLS AND CEILING.
  
 PER NFPA 37, INSTALLATION AND USE OF STATIONARY
 COMBUSTION ENGINES AND GAS TURBINES
  
 6.6.3.3 THE FILL PIPE FOR EACH TANK SHALL BE PROVIDED
 ON AN
 EXTERIOR WALL OF THE ROOM OR STRUCTURE ENCLOSING THE
 TANK AT A
 POINT AT LEAST 600 MM (24 IN.) FROM ANY BUILDING
 OPENING AT
 THE SAME OR LOWER LEVEL.
  
 WHAT AREAS DOES THE PIPE RUN THROUGH ALONG ITS ROUTE TO
 THE TANK?
  
 PLEASE REVIEW AND CORRECT, PROVIDE DISTANCES FROM
 OPENINGS OR JUSTIFY WITH SPECIFIC CODE LANGUAGE.
  
  
 4) IT IS NOT CLEARLY INDICATED THE LOCATION OF THE VENT
 PIPE.
  
 6.7.1.1 THE VENT PIPE SHALL TERMINATE OUTSIDE THE
 BUILDING AT
 A POINT AT LEAST 600 MM (24 IN.) FROM ANY BUILDING
 OPENING AT
 THE SAME OR LOWER LEVEL.
  
 PLEASE REVIEW AND PROVIDE DETAILS.
  
  
 5) THERE APPEARS TO BE FIRE RATED CHASE WITHIN AN EXIT
 STAIRWELL.
  
 IS THIS RATED SHAFT A CHANGE FROM THE ORIGINAL DESIGN
 OR A NEW DESIGN?
  
 THERE ARE NO INDICATIONS OF THE LISTED FIRE RATING
 DESIGN.
  
 THERE ARE NO INDICATIONS OF THE INTERANL STAIRWELL
 DESIGN INCLUDING DIMENSIONS AND LOCATION OF STANDPIPES.
  
 PLEASE PROVIDE DETAILS
  
  
  
 6) THE PIPE IS LOCATED WITHIN A CHASE, HOW WILL A LEAK
 WITHIN THAT CHASE BE CONTROLLED/REPAIRED?
  
 PLEASE PROVIDE DETAILS.
  
  
  
 7) THERE IS NO INDICATIONS OF PIPE PRESSURE TESTING.
  
 PER NFPA 30, CH 27
  
 27.7 TESTING OF PIPING SYSTEMS.
 27.7.1 INITIAL TESTING. UNLESS TESTED IN ACCORDANCE
 WITH THE
 APPLICABLE SECTIONS OF ASME B31, CODE FOR PRESSURE
 PIPING, ALL
 PIPING SHALL BE TESTED BEFORE BEING COVERED, ENCLOSED,
 OR
 PLACED IN USE.
 27.7.1.1 TESTING SHALL BE DONE HYDROSTATICALLY TO 150
 PERCENT OF
 THE MAXIMUM ANTICIPATED PRESSURE OF THE SYSTEM OR
 PNEUMATICALLY
 TO 110 PERCENT OF THE MAXIMUM ANTICIPATED PRESSURE OF
 THE
 SYSTEM, AND THE TEST PRESSURE SHALL BE MAINTAINED WHILE
 A COMPLETE
 VISUAL INSPECTION OF ALL JOINTS AND CONNECTIONS IS
 CONDUCTED.
 27.7.1.2 IN NO CASE SHALL THE TEST PRESSURE BE LESS
 THAN A GAUGE
 PRESSURE OF 5 PSI (35 KPA) MEASURED AT THE HIGHEST
 POINT OF THE
 SYSTEM, AND IN NO CASE SHALL THE TEST PRESSURE BE
 MAINTAINED FOR
 LESS THAN 10 MINUTES.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE.
  
  
  
 8) THERE APPEARS TO BE A LEAK DETECTOR ASSOCOATED WITH
 THE FIRE RATED CHASE MOUNTED WITHIN THE STAIRWELL.
  
 PER NFPA 101, CHAPER 7
  
 (10) PENETRATIONS INTO, AND OPENINGS THROUGH, AN EXIT
 ENCLOSURE
 ASSEMBLY SHALL BE LIMITED TO THE FOLLOWING:
 (A) DOOR ASSEMBLIES PERMITTED BY 7.1.3.2.1(9)
 (B) *ELECTRICAL CONDUIT SERVING THE EXIT ENCLOSURE
 (C) REQUIRED EXIT DOOR OPENINGS
 (D) DUCTWORK AND EQUIPMENT NECESSARY FOR INDEPENDENT
 STAIR PRESSURIZATION
 (E) WATER OR STEAM PIPING NECESSARY FOR THE HEATING OR
 COOLING OF THE EXIT ENCLOSURE
 (F) SPRINKLER PIPING
 (G) STANDPIPES
 (H) EXISTING PENETRATIONS PROTECTED IN ACCORDANCE WITH
 8.3.5
 (I) PENETRATIONS FOR FIRE ALARM CIRCUITS, WHERE THE
 CIRCUITS
 ARE INSTALLED IN METAL CONDUIT AND THE PENETRATIONS ARE
 PROTECTED IN ACCORDANCE WITH 8.3.5
  
 THAT PIECE OF EQUIPMENT DOES NOT MEET THE REQUIRMENTS
 OF ANY OF THE ABOVE PERMITTED USUES.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 9) IT IS UNCLEAR IF THERE WILL BE STATIC FUEL WITHIN
 THE PIPING AT ANYL TIME.
  
 PLEASE PROVIDE A SEQUENCE OF FILLING OPERATIONS.
  
  
  
 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  