2019-05-22 10:27:25 | PLAN |
| REVIEW COMMENTS |
| 2ND REVIEW: FBC SIXTH EDITION (2017) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE SITE PLANS THAT WERE SUBMITTED DO NOT SHOW THE |
| PROPOSED STRUCTURE. PROVIDE TWO SETS OF A SITE PLAN OR |
| SURVEY THAT SHOWS THE PROPOSED STRUCTURE AND DISTANCES |
| TO LOT LINES. FBC 107.2.1 |
| |
| 2) THE PROPOSED SIX FOOT HIGH CONSTRUCTION FENCE MAY |
| NOT BE ADEQUATE PROTECTION IN AREAS WHERE CONSTRUCTION |
| BARRIERS ARE REQUIRED. THE REQUIREMENTS ARE BASED ON |
| THE HEIGHT OF THE BUILDING AND THE DISTANCE FROM |
| CONSTRUCTION TO THE LOT LINE. SEE FBC 3306.1 PROTECTION |
| REQUIRED. PEDESTRIANS SHALL BE PROTECTED DURING |
| CONSTRUCTION, REMODELING AND DEMOLITION ACTIVITIES AS |
| REQUIRED BY THIS CHAPTER AND TABLE 3306.1. SIGNS SHALL |
| BE PROVIDED TO DIRECT PEDESTRIAN TRAFFIC. |
| |
| 2A) FBC 3306.5 BARRIERS. |
| BARRIERS SHALL BE NOT LESS THAN 8 FEET (2438 MM) IN |
| HEIGHT AND SHALL BE PLACED ON THE SIDE OF THE WALKWAY |
| NEAREST THE CONSTRUCTION. BARRIERS SHALL EXTEND THE |
| ENTIRE LENGTH OF THE CONSTRUCTION SITE. OPENINGS IN |
| SUCH BARRIERS SHALL BE PROTECTED BY DOORS THAT ARE |
| NORMALLY KEPT CLOSED. |
| |
| 2B) FBC 3306.6 BARRIER DESIGN. |
| BARRIERS SHALL BE DESIGNED TO RESIST LOADS REQUIRED IN |
| CHAPTER 16 UNLESS CONSTRUCTED AS FOLLOWS: |
| 1.BARRIERS SHALL BE PROVIDED WITH 2-INCH BY 4-INCH (51 |
| MM BY 102 MM) TOP AND BOTTOM PLATES. |
| 2.THE BARRIER MATERIAL SHALL BE BOARDS NOT LESS THAN |
| 3/4-INCH (19.1 MM) THICK OR WOOD STRUCTURAL PANELS NOT |
| LESS THAN 1/4-INCH (6.4 MM) THICK. |
| 3.WOOD STRUCTURAL USE PANELS SHALL BE BONDED WITH AN |
| ADHESIVE IDENTICAL TO THAT FOR EXTERIOR WOOD STRUCTURAL |
| USE PANELS. |
| 4.WOOD STRUCTURAL USE PANELS 1/4 INCH (6.4 MM) OR 5/16 |
| INCH (23.8 MM) IN THICKNESS SHALL HAVE STUDS SPACED NOT |
| MORE THAN 2 FEET (610 MM) ON CENTER. |
| 5.WOOD STRUCTURAL USE PANELS 3/8 INCH (9.5 MM) OR 1/2 |
| INCH (12.7 MM) IN THICKNESS SHALL HAVE STUDS SPACED NOT |
| MORE THAN 4 FEET (1219 MM) ON CENTER PROVIDED A 2-INCH |
| BY 4-INCH (51 MM BY 102 MM) STIFFENER IS PLACED |
| HORIZONTALLY AT MID-HEIGHT WHERE THE STUD SPACING IS |
| GREATER THAN 2 FEET (610 MM) ON CENTER. |
| 6.WOOD STRUCTURAL USE PANELS 5/8 INCH (15.9 MM) OR |
| THICKER SHALL NOT SPAN OVER 8 FEET (2438 MM). |
| |
| 2C) FBC 3306.7 COVERED WALKWAYS. |
| COVERED WALKWAYS SHALL HAVE A CLEAR HEIGHT OF NOT LESS |
| THAN 8 FEET (2438 MM) AS MEASURED FROM THE FLOOR |
| SURFACE TO THE CANOPY OVERHEAD. ADEQUATE LIGHTING SHALL |
| BE PROVIDED AT ALL TIMES. COVERED WALKWAYS SHALL BE |
| DESIGNED TO SUPPORT ALL IMPOSED LOADS. IN NO CASE SHALL |
| THE DESIGN LIVE LOAD BE LESS THAN 150 PSF (7.2 KN/M2) |
| FOR THE ENTIRE STRUCTURE. |
| |
| 3) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |
| |
| |
| |
| |
| |