Plan Review Notes For Permit 19050376
Permit Number 19050376
Review Stop B
Sequence Number 2
Notes
Date Text
2019-05-22 10:27:25PLAN
 REVIEW COMMENTS
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SITE PLANS THAT WERE SUBMITTED DO NOT SHOW THE
 PROPOSED STRUCTURE. PROVIDE TWO SETS OF A SITE PLAN OR
 SURVEY THAT SHOWS THE PROPOSED STRUCTURE AND DISTANCES
 TO LOT LINES. FBC 107.2.1
  
 2) THE PROPOSED SIX FOOT HIGH CONSTRUCTION FENCE MAY
 NOT BE ADEQUATE PROTECTION IN AREAS WHERE CONSTRUCTION
 BARRIERS ARE REQUIRED. THE REQUIREMENTS ARE BASED ON
 THE HEIGHT OF THE BUILDING AND THE DISTANCE FROM
 CONSTRUCTION TO THE LOT LINE. SEE FBC 3306.1 PROTECTION
 REQUIRED. PEDESTRIANS SHALL BE PROTECTED DURING
 CONSTRUCTION, REMODELING AND DEMOLITION ACTIVITIES AS
 REQUIRED BY THIS CHAPTER AND TABLE 3306.1. SIGNS SHALL
 BE PROVIDED TO DIRECT PEDESTRIAN TRAFFIC.
  
 2A) FBC 3306.5 BARRIERS.
 BARRIERS SHALL BE NOT LESS THAN 8 FEET (2438 MM) IN
 HEIGHT AND SHALL BE PLACED ON THE SIDE OF THE WALKWAY
 NEAREST THE CONSTRUCTION. BARRIERS SHALL EXTEND THE
 ENTIRE LENGTH OF THE CONSTRUCTION SITE. OPENINGS IN
 SUCH BARRIERS SHALL BE PROTECTED BY DOORS THAT ARE
 NORMALLY KEPT CLOSED.
  
 2B) FBC 3306.6 BARRIER DESIGN.
 BARRIERS SHALL BE DESIGNED TO RESIST LOADS REQUIRED IN
 CHAPTER 16 UNLESS CONSTRUCTED AS FOLLOWS:
 1.BARRIERS SHALL BE PROVIDED WITH 2-INCH BY 4-INCH (51
 MM BY 102 MM) TOP AND BOTTOM PLATES.
 2.THE BARRIER MATERIAL SHALL BE BOARDS NOT LESS THAN
 3/4-INCH (19.1 MM) THICK OR WOOD STRUCTURAL PANELS NOT
 LESS THAN 1/4-INCH (6.4 MM) THICK.
 3.WOOD STRUCTURAL USE PANELS SHALL BE BONDED WITH AN
 ADHESIVE IDENTICAL TO THAT FOR EXTERIOR WOOD STRUCTURAL
 USE PANELS.
 4.WOOD STRUCTURAL USE PANELS 1/4 INCH (6.4 MM) OR 5/16
 INCH (23.8 MM) IN THICKNESS SHALL HAVE STUDS SPACED NOT
 MORE THAN 2 FEET (610 MM) ON CENTER.
 5.WOOD STRUCTURAL USE PANELS 3/8 INCH (9.5 MM) OR 1/2
 INCH (12.7 MM) IN THICKNESS SHALL HAVE STUDS SPACED NOT
 MORE THAN 4 FEET (1219 MM) ON CENTER PROVIDED A 2-INCH
 BY 4-INCH (51 MM BY 102 MM) STIFFENER IS PLACED
 HORIZONTALLY AT MID-HEIGHT WHERE THE STUD SPACING IS
 GREATER THAN 2 FEET (610 MM) ON CENTER.
 6.WOOD STRUCTURAL USE PANELS 5/8 INCH (15.9 MM) OR
 THICKER SHALL NOT SPAN OVER 8 FEET (2438 MM).
  
 2C) FBC 3306.7 COVERED WALKWAYS.
 COVERED WALKWAYS SHALL HAVE A CLEAR HEIGHT OF NOT LESS
 THAN 8 FEET (2438 MM) AS MEASURED FROM THE FLOOR
 SURFACE TO THE CANOPY OVERHEAD. ADEQUATE LIGHTING SHALL
 BE PROVIDED AT ALL TIMES. COVERED WALKWAYS SHALL BE
 DESIGNED TO SUPPORT ALL IMPOSED LOADS. IN NO CASE SHALL
 THE DESIGN LIVE LOAD BE LESS THAN 150 PSF (7.2 KN/M2)
 FOR THE ENTIRE STRUCTURE.
  
 3) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
  
  
  
  
  