Plan Review Notes
Plan Review Notes For Permit 19050376
Permit Number 19050376
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-05-14 15:54:21THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) AN EMERGENCY ENTRANCE/EXIT IS INDICATED WITH NO
 DIMENSION.
  
 PER NFPA 1
  
 18.2.3 FIRE DEPARTMENT ACCESS ROADS.
 18.2.3.1 REQUIRED ACCESS.
 18.2.3.1.1 APPROVED FIRE DEPARTMENT ACCESS ROADS SHALL
 BE PROVIDED
 FOR EVERY FACILITY, BUILDING, OR PORTION OF A BUILDING
 HEREAFTER
 CONSTRUCTED OR RELOCATED.
 18.2.3.1.2 FIRE DEPARTMENT ACCESS ROADS SHALL CONSIST
 OF ROADWAYS, FIRE
 LANES, PARKING LOT LANES, OR A COMBINATION THEREOF.
  
 18.2.3.4.1 DIMENSIONS.
 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED
 WIDTH OF NOT LESS THAN 20 FT (6.1 M).
  
 PLEASE PROVIDE AN APPLICABLE SIZED OPENING.
  
  
  
 2) IT IS STRONGLY ENCOURAGED TO HAVE THE GATE LOCKED
 WITH A KNOX PADLOCK FOR 24 HE EMERGENCY ACCESS.
  
 18.2.2.2 ACCESS TO GATED SUBDIVISIONS OR DEVELOPMENTS.
 THE AHJ
 SHALL HAVE THE AUTHORITY TO REQUIRE FIRE DEPARTMENT
 ACCESS BE PROVIDED
 TO GATED SUBDIVISIONS OR DEVELOPMENTS THROUGH THE USE
 OF AN APPROVED
 DEVICE OR SYSTEM.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  