Plan Review Notes For Permit 19050360 |
Permit Number |
19050360 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-05-14 06:57:37 | GAS 2ND REVIEW**DENIED** | | | | 1) NOT ADDRESSED**CITY RECORDS ( PERMIT # 04081048 SHOW | | OTHER GAS EQUIPMENT (DRYER) .LIST THE BTU LOAD OF EACH | | APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER | | TO THE 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES | | G2413.4 (1 ) THROUGH G2413.4 (21). | | | | 2) ANSWERED**PERMIT APPLICATION CALLS OUT RANGE BUT NO | | RANGE SHOW ON GAS PLAN OR ISOMETRIC. LIST THE BTU LOAD | | OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM. | | REFER TO THE 2017 FBC-RES. SEC. G2413.3, G2413.4 AND | | TABLES G2413.4 (1 ) THROUGH G2413.4 (21). | | | | 3) NOT ADDRESSED** PROVIDE INSTALLATION MANUAL FOR NEW | | TANKLESS WATER HEATER. MANUAL PROVIDED IS THE VENTING | | FOR AN INDOOR MODEL. PLAN CALLS OUT AN OUTDOOR | | MODEL.PLEASE CLARIFY. FBC 107.2.1 | | | | 4) ANSWERED** | | | | 5) NOT ADDRESSED**A PLUMBING AND ELECTRICAL PERMIT IS | | REQUIRED FOR THE INSTALLATION OF A TANKLESS WATER | | HEATER, NO OTHER APPLICATIONS HAVE BEEN SUBMITTED. FBC | | 105.1 | | | | | | TIM HUNT | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | CITY OF WEST PALM BEACH | | 561-248-2703 | | [email protected] | | [email protected] | | | | |
|