2019-05-14 06:57:37GAS 2ND REVIEW**DENIED**
  
 1) NOT ADDRESSED**CITY RECORDS ( PERMIT # 04081048 SHOW
 OTHER GAS EQUIPMENT (DRYER) .LIST THE BTU LOAD OF EACH
 APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER
 TO THE 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
  
 2) ANSWERED**PERMIT APPLICATION CALLS OUT RANGE BUT NO
 RANGE SHOW ON GAS PLAN OR ISOMETRIC. LIST THE BTU LOAD
 OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM.
 REFER TO THE 2017 FBC-RES. SEC. G2413.3, G2413.4 AND
 TABLES G2413.4 (1 ) THROUGH G2413.4 (21).
  
 3) NOT ADDRESSED** PROVIDE INSTALLATION MANUAL FOR NEW
 TANKLESS WATER HEATER. MANUAL PROVIDED IS THE VENTING
 FOR AN INDOOR MODEL. PLAN CALLS OUT AN OUTDOOR
 MODEL.PLEASE CLARIFY. FBC 107.2.1
  
 4) ANSWERED**
  
 5) NOT ADDRESSED**A PLUMBING AND ELECTRICAL PERMIT IS
 REQUIRED FOR THE INSTALLATION OF A TANKLESS WATER
 HEATER, NO OTHER APPLICATIONS HAVE BEEN SUBMITTED. FBC
 105.1
  
  