2019-06-18 15:27:35CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THERE IS A CONFLICT BETWEEN THE RISER DIAGRAM AND
 THE PANEL SCHEDULES. IS PANEL B FED FROM PANEL A, OR IS
 IT FED FROM PANEL B DISCONNECT? WHERE IS PANEL B
 DISCONNECT FED FROM? THERE IS CONFLICT ALSO WITH WIRE
 SIZE WITH PANEL A STATING THAT PANEL B IS FED WITH 6
 GAUGE WIRE AND THE RISER STATING THAT IT IS FED WITH 1
 GAUGE WIRE. PROVIDE CLARIFICATIONS AND/OR CORRECTIONS
 AS NEEDED. NEC 215.5; WPB FBC 107.2.1
 2. PROVIDE LOAD CALCULATION FOR PANEL B. IF THIS PANEL
 IS FED WITH LESS THAN A 100 AMP FEEDER, DEMAND FACTORS
 ARE NOT PERMITTED TO BE USED. NEC 220; FBC RE E3602.2
 OR E3701.2 AS APPLICABLE.
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 4. PROVIDE GFCI PROTECTION FOR GAS WATER HEATER IGNITOR
 RECEPTACLE. NEC 210.8; FBC RE E3902.3
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 6. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE
 OUTLETS IN GARAGE, INCLUDING THE GARAGE DOOR OPENER.
 PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2
 7. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1,
 801.2, OR 901.2 AS APPLICABLE.
 8. THERE ARE TWO SHEETS NAMED E1.0. THE SECOND ONE HAS
 THE PLUMBING RISER ON IT. PROVIDE CORRECTION. WPB FBC
 107.2.1
 9. THE CONDUIT FROM METER CAN TO MAIN SERVICE
 DISCONNECT SHOULD NOT INCLUDE AN EQUIPMENT GROUNDING
 CONDUCTOR. PROVIDE CORRECTION.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER