2019-06-18 15:27:35 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. THERE IS A CONFLICT BETWEEN THE RISER DIAGRAM AND |
| THE PANEL SCHEDULES. IS PANEL B FED FROM PANEL A, OR IS |
| IT FED FROM PANEL B DISCONNECT? WHERE IS PANEL B |
| DISCONNECT FED FROM? THERE IS CONFLICT ALSO WITH WIRE |
| SIZE WITH PANEL A STATING THAT PANEL B IS FED WITH 6 |
| GAUGE WIRE AND THE RISER STATING THAT IT IS FED WITH 1 |
| GAUGE WIRE. PROVIDE CLARIFICATIONS AND/OR CORRECTIONS |
| AS NEEDED. NEC 215.5; WPB FBC 107.2.1 |
| 2. PROVIDE LOAD CALCULATION FOR PANEL B. IF THIS PANEL |
| IS FED WITH LESS THAN A 100 AMP FEEDER, DEMAND FACTORS |
| ARE NOT PERMITTED TO BE USED. NEC 220; FBC RE E3602.2 |
| OR E3701.2 AS APPLICABLE. |
| 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC |
| RE E3606.3 |
| 4. PROVIDE GFCI PROTECTION FOR GAS WATER HEATER IGNITOR |
| RECEPTACLE. NEC 210.8; FBC RE E3902.3 |
| 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| 210.8(D); FBC RE E3902.10 |
| 6. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE |
| OUTLETS IN GARAGE, INCLUDING THE GARAGE DOOR OPENER. |
| PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2 |
| 7. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL |
| BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- |
| AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND |
| POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH |
| AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC |
| 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1, |
| 801.2, OR 901.2 AS APPLICABLE. |
| 8. THERE ARE TWO SHEETS NAMED E1.0. THE SECOND ONE HAS |
| THE PLUMBING RISER ON IT. PROVIDE CORRECTION. WPB FBC |
| 107.2.1 |
| 9. THE CONDUIT FROM METER CAN TO MAIN SERVICE |
| DISCONNECT SHOULD NOT INCLUDE AN EQUIPMENT GROUNDING |
| CONDUCTOR. PROVIDE CORRECTION. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |