Date |
Text |
2019-05-15 13:08:58 | PLUMBING 1ST REVISION REVIEW**DENIED** |
| |
| 1) A GAS TANKLESS WATER HEATER IS CALLED OUT ON THE |
| R405-2017 FORM LISTED @ .80 E.F. THE FEDERAL MIN |
| EFFICIENCY AS OF 12/29/2016 IS .82%. REFER TO FEDERAL |
| REGISTER VOL. 81, NO. 250. |
| |
| 2) PROVIDE LOCATION OF THE ACCESSIBLE SHUT OFF VALVES |
| FOR THE STACKABLE WASHING AND DRYER. FBC-R P2903.9.3 |
| |
| 3)PROVIDE NOTE THAT FREE STANDING TUB VALVE SHALL BE |
| TEMPERED BY AN ASSE 1070 DEVICE PER FBC-R P 2713.3 OR |
| MEET ONE OF THE REQUIREMENTS IN P2708.4 |
| |
| 4) ISOMETRIC DRAWING ON SHT. E1.0 MASTER BATHROOM SHOW |
| 2 FIXTURES BEYOND THE ACTUAL VENT. ONLY ONE IS |
| PERMITTED IN A WET VENT SYSTEM. FBC-R P3108.2.1 AND THE |
| FOYER BATH SHALL HAVE EACH WET-VENTED FIXTURE CONNECT |
| TO THE HORIZONTALLY BRANCH IS PART OF THE WET VENT. |
| FBC-R P3108.1 |
| |
| 5) SHT. E1.0 PANEL SCHEDULE CALLS OUT ELC TANKLESS |
| 4.5KW WHILE THE R405-2017 FORM CALLS OUT GAS TANKLESS. |
| PLEASE CLARIFY AND PROVIDE LOCATION PLAN OF TANKLESS |
| WATER HEATER. FBC 107.3.5 |
| |
| 6) PROVIDE COMPLETE INSTALLATION MANUAL FOR TANKLESS |
| WATER HEATER TO INCLUDE HEAT RISE CHARTS. FBC 107.2.1 |
| |
| 7) PROVIDE SHOWER PAN DETAIL TO SHOW PRE-PITCH AS |
| REQUIRED IN FBC-R P 2709.3 |
| |
| 8) IN THE PLUMBING NOTES #14 YOU CALL YOU FOR A HOT |
| WATER RETURN SYSTEM. PLEASE ADD NOTE ALL HOT WATER |
| PIPING OUTSIDE THE CONDITIONED SPACE SHALL BE INSULATED |
| TO A MIN R-3. FBC-ENERGY 403.5.3. |
| |
| |
| |
| |
| TIM HUNT |
| PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |
| BUILDING DIVISION |
| CITY OF WEST PALM BEACH |
| 401 CLEMATIS STREET, 1ST FLOOR |
| WEST PALM BEACH, FL 33401 |
| 561-248-2703 |
| [email protected] |
| [email protected] |