2019-05-22 16:13:15 | MECHANICAL PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER, PX3169 |
| 1&2 FAMILY PLANS EXAMINER, SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH |
| EDITION |
| FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| 1. PROVIDE AN ACCURATELY COMPLETED ENERGY SUBMITTAL. |
| CEILING INSULATION VALUE ON ENERGY SUBMITTAL DOES NOT |
| MATCH APPROVED DESIGN. |
| FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| COMPLIANCE BY SECTION 405. |
| |
| 2. PLAN SHOWS 3 SYSTEMS, ENERGY SUBMITTAL SHOWS 1 |
| SYSTEM. PLEASE CLARIFY. |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 3. ENERGY SUBMITTAL SPECIFIES GAS FUELED TANKLESS WATER |
| HEATER. PLANS SPECIFY ELECTRIC WATER HEATER. PLEASE |
| CLARIFY. |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 4. PROVIDE PRODUCT APPROVAL FOR CU TIE-DOWN. |
| FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| SPECIFICALLY, PROVIDE CU TIE-DOWN SUBMITTALS. |
| |
| 5. MECHANICAL PLAN M.1 DOES NOT SHOW LOCATION OF CU #2 |
| AND CU #3. PLEASE CLARIFY. |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED. |
| |
| |
| |
| |
| |
| |