2019-05-20 11:43:57ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PG. E1.0
  
 SEVERAL BEDROOMS HAVE NO SMOKE ALARMS/ CO ALARMS
  
 FOYER MAY NEED OUTLETS PER FBC E3901.11
  
 PENINSULAR OUTLETS IN THE KITCHEN PER FBC E3901.4.3
  
 RISER DIAGRAM SHOWS 300 AMPERE SERVICE BUT WIRE SIZE IS
 ONLY GOOD FOR 150 AMPERES
  
 PANEL SIZE SHOWS 200 AMPERES BEING FED BY A 300 AMPERE
 SWITCH.
  
 PANEL BOARD IDENTIFICATION
 E3706.2PANELBOARD CIRCUIT IDENTIFICATION.
 ALL CIRCUITS AND CIRCUIT MODIFICATIONS SHALL BE LEGIBLY
 IDENTIFIED AS TO THEIR CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE.
 THE IDENTIFICATION SHALL INCLUDE AN APPROVED DEGREE OF
 DETAIL THAT ALLOWS EACH CIRCUIT TO BE DISTINGUISHED
 FROM ALL OTHERS.
 SPARE POSITIONS THAT CONTAIN UNUSED OVERCURRENT DEVICES
 OR SWITCHES SHALL BE DESCRIBED ACCORDINGLY. THE
 IDENTIFICATION
 SHALL BE INCLUDED IN A CIRCUIT DIRECTORY LOCATED ON THE
 FACE OF THE PANELBOARD ENCLOSURE OR INSIDE THE PANEL
 DOOR. CIRCUITS
 SHALL NOT BE DESCRIBED IN A MANNER THAT DEPENDS ON
 TRANSIENT CONDITIONS OF OCCUPANCY. [408.4(A)]