2019-05-23 15:38:02CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. RISER DIAGRAM HAS BEEN REMOVED FROM PLAN. IF THE
 ELCTRICAL PANELS OR SERVICE IS BEING REPLACED, THE
 RISER DIAGRAM IS REQUIRED. IF THE MAIN SERVICE
 DISCONNECT IS BEING REPLACED, THEN AIC CALCULATION AND
 AIC RATING OF SERVICE EQUIPMENT IS REQUIRED. PLAN NOTE
 8 SAYS THAT THERE WILL BE A 150 AMP PANEL INSTALLED.
 THIS NOTE DOES NOT SHOW WHERE IT IS LOCATED ON PLAN.
 NOTE 10 STATES THAT THERE WILL BE A 200 AMP PANEL
 INSTALLED. CORRECT DISCREPANCIES AND PROVIDE RISER
 DIAGRAM. NEC 110.9, 110.10, 215.5; FBC RE E3706.1,
 E3608.1, E3606.3, E3609.3; WPB FBC 107.2.1 (RISER
 DIAGRAM STILL NOT PROVIDED, A PICTURE OF THE RE-BUILT
 SERVICE IS NOT ACCEPTABLE. PROVIDE ACCURATE RISER
 DIAGRAM INCLUDING WIRE SIZES AND GROUNDING DETAIL.
 ALSO, THERE STILL IS A NOTE #8, BUT THIS IS NOT SHOWN
 ON THE PLAN. WHERE WAS THE OLD PANEL REMOVED FROM?
 PROVIDE CORRECTIONS.)
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved