2019-05-16 09:20:25 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. RISER DIAGRAM HAS BEEN REMOVED FROM PLAN. IF THE |
| ELCTRICAL PANELS OR SERVICE IS BEING REPLACED, THE |
| RISER DIAGRAM IS REQUIRED. IF THE MAIN SERVICE |
| DISCONNECT IS BEING REPLACED, THEN AIC CALCULATION AND |
| AIC RATING OF SERVICE EQUIPMENT IS REQUIRED. PLAN NOTE |
| 8 SAYS THAT THERE WILL BE A 150 AMP PANEL INSTALLED. |
| THIS NOTE DOES NOT SHOW WHERE IT IS LOCATED ON PLAN. |
| NOTE 10 STATES THAT THERE WILL BE A 200 AMP PANEL |
| INSTALLED. CORRECT DISCREPANCIES AND PROVIDE RISER |
| DIAGRAM. NEC 110.9, 110.10, 215.5; FBC RE E3706.1, |
| E3608.1, E3606.3, E3609.3; WPB FBC 107.2.1 |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |