2019-10-21 17:04:54 | 3RD REVIEW: 19050677 |
| |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PLUMBING COMMENTS: IT DOES NOT APPEAR THAT THE PLUMBING |
| COMMENTS HAVE BEEN ADDRESSED. WITH NO RESPONSE LETTER |
| IT IS DIFFICULT TO DETERMINE WHAT . IF ON THE THIRD THE |
| SAME COMMENTS HAVE NOT BEEN REPLIED TO 3X THE PLAN |
| REVIEW FEE WILL BE CHARGED. PLEASE CONTACT REVIEWER |
| PRIOR TO RESUMITTAL TO CLARIFY SCOPE OF WORK SEE |
| CONTACT INFO BELOW. |
| |
| 1. PROVIDE FLOOR PLAN SHOWING LOCATION OF NEW BATHROOM |
| LAVATORY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 2. PLEASE CLARIFY IS THIS A REPLACEMENT OF EXITING SINK |
| ARE ARE YOU ADDING A SINK. PER WPB AMEND TO FBC 107.2.1 |
| |
| 3. PROVIDE DETAILS FOR THE SINK THAT MEET FBC ACC 606.2 |
| CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING WITH |
| 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE AND |
| TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED. |
| 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED |
| WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER |
| SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH |
| FLOOR OR GROUND. |
| |
| 4. PROVIDE WATER AND SANITARY ISOMETRIC DRAWINGS. PER |
| WPB AMEND TO FBC 107.3.5.1.3(13) |
| |
| 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| |