Plan Review Notes For Permit 19050303 |
Permit Number |
19050303 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-07-16 09:35:26 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #19050303 | | 7/16/19 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE PLAN SHOWS TWO NEW OFFICES TO BE CONSTRUCTED. | | REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING CODE | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE | | OFFICES PER TABLE 403.3.1.1 FBC-17 MECHANICAL. PROVIDE | | A SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED | | CFMS OF OUTDOOR AIR. | | | | 2) INDICATE HOW AIR IS BEING SUPPLIED TO AND RETURNED | | FROM THE NEW OFFICES- SHOW THE REQUIRED DUCT | | ALTERATIONS- SECTION 603.1 FBC M. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | BUILDING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|