Plan Review Notes
Plan Review Notes For Permit 19050303
Permit Number 19050303
Review Stop M
Sequence Number 1
Notes
Date Text
2019-07-16 09:35:261ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19050303
 7/16/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PLAN SHOWS TWO NEW OFFICES TO BE CONSTRUCTED.
 REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 OFFICES PER TABLE 403.3.1.1 FBC-17 MECHANICAL. PROVIDE
 A SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED
 CFMS OF OUTDOOR AIR.
  
 2) INDICATE HOW AIR IS BEING SUPPLIED TO AND RETURNED
 FROM THE NEW OFFICES- SHOW THE REQUIRED DUCT
 ALTERATIONS- SECTION 603.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved