2019-06-03 09:38:11 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19050303 |
| ADD: 3601 S DIXIE HWY |
| CONT: J & V SERVICES |
| TEL: 561-601-1614 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. JUNE 02/ 2019 |
| ACTION: DENIED |
| |
| 1A) THERE IS A DISCREPANCY BETWEEN THE SCOPE OF WORK |
| LISTED ON THE PERMIT APPLICATION (INTERIOR REMODELING |
| AND THE INSTALLATION OF A NEW BATHROOM SINK) AND THE |
| SCOPE OF WORK AND LOCATION LISTED ON SHEET G-001 THE |
| COVERSHEET. SHEET G-001 THE COVERSHEET LIST THE WORK |
| BEING COMPLETED IN THE CITY OF MIAMI, MIAMI-DADE |
| COUNTY, MIAMI DEPARTMENT PUBLIC WORKS, FLOOD ZONES, |
| DEWATERING AND TRENCHING REQUIREMENTS UNDER THE |
| HEADINGS OF SITE WORK, GENERAL NOTES & UNDERGROUND |
| CONTRACTORS. |
| 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED, A |
| DISCREPANCY IN PLANS AND PERMIT APPLICATION DESCRIPTION |
| OF WORK. |
| |
| 1B) THE PERMIT APPLICATION INDICATES UNDER THE |
| DESCRIPTION OF WORK, INTERIOR REMODELING AND THE |
| INSTALLATION OF A NEW BATHROOM SINK. SHEET A-101 LIST |
| IN DETAIL # 1 INDICATES 2 NEW OFFICES AND NO RESTROOM |
| OR NEW BATHROOM SINK? A RED TAG WAS WRITTEN AND LISTED |
| IN COMPUTER ON 4/22/19 FOR NEW WALLS, ELECTRIC AND |
| PLUMBING. THERE ARE NO PLUMBING SHEETS INCORPORATED IN |
| THESE PLANS? ADDITIONAL INFORMATION IS REQUIRED, A |
| DISCREPANCY IN PLANS AND THE RED TAG WRITTEN ON |
| 04/22/19 FOR WORK TO BE COVERED UNDER THIS PERMIT, |
| DISCREPANCY OF DESCRIPTION OF WORK. 107.2.1.2. |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 2) PLEASE SEE COMMENTS FROM PLUMBING PLAN REVIEWER IF |
| THERE IS TO BE A NEW OR REMODELED RESTROOM. |
| 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. |
| 107.3.5.1.1 BUILDING. |
| 2017 FBC-EXISTING BUILDING CODE 301.1GENERAL. THE |
| REPAIR, ALTERATION, CHANGE OF OCCUPANCY, ADDITION OR |
| RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY WITH |
| ONE OF THE METHODS LISTED IN SECTIONS 301.1.1 THROUGH |
| 301.1.3 AS SELECTED BY THE APPLICANT. SECTIONS 301.1.1 |
| THROUGH 301.1.3 SHALL NOT BE APPLIED IN COMBINATION |
| WITH EACH OTHER. |
| |
| 3) NO MECHANICAL PLANS WERE SUBMITTED NOR REVIEW STOP |
| ADDED BUT COMPLIANCE FOR TOILET ROOMS WOULD BE REQUIRED |
| UNDER THE 2017 MECHANICAL CODE SECTION 403.3.2.3 LOCAL |
| EXHAUST, AND TABLE 403.3.1.1 PUBLIC SPACES, TOLIET |
| ROOMS FOOTNOTE (G). |
| |
| 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |
| |