2019-05-16 16:11:54 | PLUMBING 1ST REVIEW**DENIED** |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| 1) SHT P2 SHOW 2 (B) UNIT SPACES. I BELIEVE THIS SHOULD |
| BE C? PLEASE CLARIFY. FBC 107.2.1 |
| |
| 2) PLEASE CLARIFY YOU INTENT IS TO HAVE A TANKLESS AT |
| EACH SET OF SERVICE SINKS? SHT. P2 FLAT DRAWING DOES |
| NOT SHOW HWH AT BAY'S B & E AND ALSO C & F NOT SHOWN ON |
| THE WATER ISOMETRIC. FBC 107.3.5 |
| |
| 3) TANKLESS MODEL CALLED OUT IS A LOW FLOW MODEL(.5 GPM |
| MAX) AND IS NOT CAPABLE OF PRODUCING HOT WATER AS |
| REQUIRED FBC-PLB 607.1 @ THE MIN 3 GPM THE SERVICE SINK |
| IS REQUIRED TO HAVE TO 1 SINK LET ALONG SUPPLING 2 |
| SERVICE SINKS. FBC-PLB 604.3. HEATER SHALL BE SIZED SO |
| AS TO PRODUCE HOT WATER 110F TO ALL FIXTURE IT SERVES |
| AT FULL DEMAND. |
| |
| 4) SHT. A-5 SHALL SHOW THE MOUNTING OF THE GRAB BAR @ |
| 36" TO THE TOP GRIPPING SURFACE AND NOT THE CENTER AS |
| SHOWN. FBC-ACC 609.4 |
| |
| 5) SHT. A5 SHALL SHOW THE MOUNTING OF THE MIRROR @ 40" |
| TO THE REFLECTIVE SURFACE AND NOT THE BOTTOM EDGE AS |
| SHOWN. FBC-ACC 603.3 |
| |
| 6) SHT. P2 SHALL SHOW THE MOUNTING OF THE TOILET PAPER |
| HOLDER 7"-9" FROM THE FRONT LIP OF THE TOILET EDGE. |
| FBC-ACC 604.7 |
| |
| 7) SHT. A.03 PROVIDE THE TOILET CLEAR FLOOR SPACE IN |
| BOTH RESTROOMS. FBC-ACC 604.3.1 |
| |
| 8) SHT. A.03 HAS THE REAR GRAB BAR ACROSS FROM THE |
| TOILET ON THE MEN'S AND IS MISSING ALTOGETHER ON THE |
| WOMENS. FBC-ACC 604.5.2 |
| |
| 9) IS THERE AN RPZ BACKFLOW DEVICE CURRENTLY PROTECTING |
| THE CITY'S WATER SYSTEM AT THIS PROPERTY? FBC |
| 107.2.1.IF NOT ONE WILL BE REQUIRED AND A SEPARATE |
| PLUMBING BACKFLOW PERMIT APPLICATION SHALL BE |
| SUBMITTED. WPB CROSS CONNECTION MANUAL 2017. CITY |
| ORD.#2853-95. |
| |
| |
| |
| |
| |