2019-05-20 17:39:54 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #19050186 |
| 5/20/19 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE PREVIOUSLY UNCONDITIONED WAREHOUSE NOW BEING |
| SUBDIVIDED INTO INDIVIDUAL CONDITIONED STUDIOS MUST BE |
| IN FULL COMPLIANCE WITH THE 2017 FLORIDA ENERGY |
| CONSERVATION CODE- SEE SECTION C503.2 FBC EC. THE |
| SUBMITTED C402 ENERGY FORM CANNOT BE USED TO SHOW FULL |
| COMPLIANCE BECAUSE IT ONLY REQUIRES COMPLAINCE DATA FOR |
| COMPONENTS AND SYSTEMS BEING CHANGED. REFER TO SECTION |
| C101.5.1 FOR APPROVED COMPLIANCE MATERIALS I.E |
| ENERGYGAUGE SUMMIT SOFTWARE. |
| |
| 2) SHEET M1: ART STUDIOS REQUIRE EXHAUST SYSTEMS THAT |
| ARE SIZED AT A RATE OF 0.7 CFMS PER SF. PER TABLE |
| 403.3.1.1 FBC M. PLEASE REVISE THE PLANS AND |
| VENTILATION CALCULATIONS ACCORDINGLY. |
| |
| 3) THE AC LOAD CALCULATIONS FOR STUDIOS B, C, D, E, AND |
| F REQUIRE THE ENGINEER'S SEAL AND SIGNATURE. ONLY THE |
| CALCS FOR STUDIO A HAVE BEEN SIGNED AND SEALED. AN |
| ACCEPTABLE ALTERNATIVE WOULD BE A SIGNED AND SEALED |
| COVER SHEET THAT LISTS ALL OF THE STUDIO CALCULATIONS- |
| SECTION 61G15-23.002 FAC. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |