2019-05-28 11:27:54 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. RISER DIAGRAM SHOWS FEEDER NUMBER 1 AS HAVING A #1 |
| EQUIPMENT GROUNDING CONDUCTOR IN THE RISER TO FPL. THIS |
| CONDUIT SHOULD NOT INCLUDE AN EQUIPMENT GROUNDING |
| CONDUCTOR. THE FEEDER FROM THE LOAD SIDE OF THE |
| DISCONNECT TO THE GUTTER IS NOT SPECIFIED AND SHOULD |
| INCLUDE THE EQUIPMENT GROUNDING CONDUCTOR. PROVIDE |
| CORRECTIONS. NEC 250.6 |
| 2. WIRE-WAY DOES NOT SHOW GROUNDING. PROVIDE CORRECTION |
| AS APPLICABLE. NEC 250.80, 250.86 |
| 3. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS |
| STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT |
| SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |