Date |
Text |
2019-08-13 08:41:37 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| |
| 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF |
| PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR |
| THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC |
| 107.1, 107.2.1, 107.3.5.1.2 (A DIGITAL PLAN REQUIRES A |
| DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY |
| VERIFICATION. PROVIDE CORRECTION. WPB FBC 107.1; FS |
| 471/481) |
| 2. CORRECTED. |
| 3. CORRECTED. |
| 4. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. |
| FBC EC C405.1, R404.1 (NOT PROVIDED.) |
| 5. CORRECTED. |
| 6. PROVIDE LOCATION OF ELECTRICAL SERVICE AND |
| ELECTRICAL PANEL TO CONFIRM CODE COMPLIANCE. WPB FBC |
| 107.2.1 (LOCATION OF SERVICE NOT PROVIDED.) |
| 7. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 9NOT |
| PROVIDED. PLAN SHOWS DETAILS FROM THE 1993 NEC, WHICH |
| IS NOT THE CURRENT CODE. ALSO, RISER DIAGRAM QUOTES NEC |
| 250.81, WHICH DOES NOT EXIST. PROVIDE UPDATES TO THESE |
| ITEMS AND PROVIDE THE IBTP PER COMMENT.) |
| 8. THE # 6 EQUIPMENT GROUNDING CONDUCTOR SHOULD NOT BE |
| INCLUDED IN THE CONDUIT FROM FROM THE METER TO THE MAIN |
| DISCONNECT SWITCH. PROVIDE CORRECTION. NEC 250.6; FBC |
| RE E3610.4 (NOT CORRECTED.) |
| 9. CORRECTED. |
| 10. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1 ( NOT |
| CORRECT. A SMOKE ALARM IS REQUIRED OUTSIDE THE SLEEPING |
| AREA, AND A CARBON MONOXIDE ALARM IS REQUIRED WITHIN 10 |
| FEET OF EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE |
| R315.1) |
| 11. CORRECTED. |
| 12. CORRECTED. |
| 13. CORRECTED. |
| 14. CORRECTED. |
| 15. CORRECTED. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |