Plan Review Notes For Permit 19050176 |
Permit Number |
19050176 |
|
Review Stop |
SIGNATURE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-08-19 16:55:21 | SIGNATURE AND SEAL REVIEW | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | | | RESULTS: DENIED | | | | DIGITAL REVIEW | | | | 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH | | FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE | | NEXT REVIEW CYCLE REQUIRE REVIEW. | | | | 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL | | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE | | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT. | | | | | 2019-08-13 08:44:54 | ELECTRICAL SHEETS: PER THE WPB AMENDMENTS TO THE FBC, | | EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED | | BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL | | PLAN REQUIRES A DIGITAL SIGNATURE WITH THE PROPER THIRD | | PARTY VERIFICATION. SELF-CERTIFICATION IS NOT | | ACCEPTABLE FOR ENGINEERS. ADDITIONALLY, THE DIGITAL | | SIGNATURE MUST INCLUDE THE STATEMENT "SIGNED AND | | SEALED" AS PER FAC 61G15-23.004. PROVIDE CORRECTION. | | WPB FBC 107.1; FS 471/481 |
|