2019-05-13 15:15:49 | PLUMBING 1ST REVIEW**DENIED** | | | | 1) PLANS SHALL BE SIGNED AND SEAL BY DESIGN | | PROFESSIONAL. FAC 471, 481 | | | | 2) PROVIDE PIPE SIZES ON PLUMBING ISOMETRIC DRAWING. | | FBC 107.3.5 | | | | 3) MASTER BATHROOM ISOMETRIC SHOW 2 LAV AND NO TUB. | | PLEASE CORRECT. FBC WPB ADMIN. 107.1 | | | | 4) SHT #3 PLUMBING NOT #2 AND #3 CALL OUT PVC PIPING TO | | BE USED ON THE EXTERIOR AND HOT WATER. PVC PIPING IS | | NOT PERMITTED/ APPROVED TO USED FOR WATER DISTRIBUTION/ | | HOT WATER PIPING. FBC-P 604.4 | | | | 5) SHT #3 CALLS UP FOR 1/2" INSULATION. PLEASE CORRECT | | AND SHOW AS R-3 MIN ON ALL HOT WATER PIPING NOT IN THE | | CONDITIONED SPACE. FBC-ENERGY R403.5.3 | | | | 6) PROVIDE R405-2017 OR R402-2017 ENERGY FORM. | | | | 7) PROVIDE SHOWER PAN DETAIL SHOWING 2% MIN AND CALL | | OUT MATERIAL TO BE USED. FBC-R P 2709.3 | | | | | | TIM HUNT | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | BUILDING DIVISION | | CITY OF WEST PALM BEACH | | 401 CLEMATIS STREET, 1ST FLOOR | | WEST PALM BEACH, FL 33401 | | 561-248-2703 | | [email protected] | | [email protected] | | | | | | | | | | | | | | | | |
|