Plan Review Notes
Plan Review Notes For Permit 19050176
Permit Number 19050176
Review Stop P
Sequence Number 1
Notes
Date Text
2019-05-13 15:15:49PLUMBING 1ST REVIEW**DENIED**
  
 1) PLANS SHALL BE SIGNED AND SEAL BY DESIGN
 PROFESSIONAL. FAC 471, 481
  
 2) PROVIDE PIPE SIZES ON PLUMBING ISOMETRIC DRAWING.
 FBC 107.3.5
  
 3) MASTER BATHROOM ISOMETRIC SHOW 2 LAV AND NO TUB.
 PLEASE CORRECT. FBC WPB ADMIN. 107.1
  
 4) SHT #3 PLUMBING NOT #2 AND #3 CALL OUT PVC PIPING TO
 BE USED ON THE EXTERIOR AND HOT WATER. PVC PIPING IS
 NOT PERMITTED/ APPROVED TO USED FOR WATER DISTRIBUTION/
 HOT WATER PIPING. FBC-P 604.4
  
 5) SHT #3 CALLS UP FOR 1/2" INSULATION. PLEASE CORRECT
 AND SHOW AS R-3 MIN ON ALL HOT WATER PIPING NOT IN THE
 CONDITIONED SPACE. FBC-ENERGY R403.5.3
  
 6) PROVIDE R405-2017 OR R402-2017 ENERGY FORM.
  
 7) PROVIDE SHOWER PAN DETAIL SHOWING 2% MIN AND CALL
 OUT MATERIAL TO BE USED. FBC-R P 2709.3
  
  