2019-07-08 06:32:14ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NOTE #1 ON PLAN SAYS "LIGHTING TO BE CONTROLLED BY
 DIGITAL TIME CLOCK OR PHOTOCELL". NOTE #1 MUST COMPLY
 WITH FBC EC 405.2.5. #2 EXTERIOR LIGHTING FOR BUILDING
 FACADE OR LANDSCAPE, MUST HAVE CONTROLS AUTOMATICALLY
 SET TO SHUT OFF LIGHTING PROGRAMMED FROM DAWN/DUSK. ALL
 TIME SWITCHES MUST HAVE MINIMUM 10HR BATTERY BACKUP.
 PLEASE COMPLY
  
 2. LIGHING SCHEDULE SHOWS S1, S2, AND S3 TYPE LIGHTS,
 BUT ONLY TYPE S1 ARE SHOWN ON PLAN? PLEASE PROVIDE
 VERIFICATION. FBC 107.2.1
  
 3. PROVIDE CUT SHEETS SHOWING UL OR OTHER NRTL LISTINGS
 FOR ALL LIGHTING AND POLES. FBC 107.2.1 NEC 90.7,110.2,
 110.3B
  
 4. PROVIDE STRUCTURAL DETAIL FOR POLE BASES AND WIND
 LOADS. FBC 1609
  
 5. SATISFY ALL ZONING REQUIREMENTS.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  