2019-07-08 06:32:14 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. NOTE #1 ON PLAN SAYS "LIGHTING TO BE CONTROLLED BY |
| DIGITAL TIME CLOCK OR PHOTOCELL". NOTE #1 MUST COMPLY |
| WITH FBC EC 405.2.5. #2 EXTERIOR LIGHTING FOR BUILDING |
| FACADE OR LANDSCAPE, MUST HAVE CONTROLS AUTOMATICALLY |
| SET TO SHUT OFF LIGHTING PROGRAMMED FROM DAWN/DUSK. ALL |
| TIME SWITCHES MUST HAVE MINIMUM 10HR BATTERY BACKUP. |
| PLEASE COMPLY |
| |
| 2. LIGHING SCHEDULE SHOWS S1, S2, AND S3 TYPE LIGHTS, |
| BUT ONLY TYPE S1 ARE SHOWN ON PLAN? PLEASE PROVIDE |
| VERIFICATION. FBC 107.2.1 |
| |
| 3. PROVIDE CUT SHEETS SHOWING UL OR OTHER NRTL LISTINGS |
| FOR ALL LIGHTING AND POLES. FBC 107.2.1 NEC 90.7,110.2, |
| 110.3B |
| |
| 4. PROVIDE STRUCTURAL DETAIL FOR POLE BASES AND WIND |
| LOADS. FBC 1609 |
| |
| 5. SATISFY ALL ZONING REQUIREMENTS. |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |