Plan Review Notes For Permit 19050027 |
Permit Number |
19050027 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-06-04 13:08:54 | PLUMBING 1ST REVIEW**DENIED** | | | | | | 1-PROVIDE CLEAR FLOOR SPACE AS REQUIRED IN | | FBC-ACC606.2, TURNING SPACE AS REQUIRED IN FBC-ACC 304, | | AND ACCESSIBLE ROUTE FBC-ACC 404 ON THE A SHEET NEW | | WORK FOR BOTH THE BREAK ROOM SINK AND CAF? SINK. BEING | | THAT THESE ARE 2 DIFFERENT SINKS BOTH SHALL APPLY WITH | | THE FLORIDA ACCESSIBILITY CODE. | | | | 2-PROVIDE SANITARY ISOMETRIC DRAWING. SHT. P 01 REFERS | | UNDER KEY NOTE (NEW VENT LINE) BUT NO ISOMETRIC | | PROVIDE. FBC 107.3.5 | | | | 3- PROVIDE DIMENSIONS OF DOORWAYS AND PATHWAYS SHOWING | | MIN ACCESSIBLE PATH. FBC 107.3.5 | | | | | | TIM HUNT | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | BUILDING DIVISION | | CITY OF WEST PALM BEACH | | 401 CLEMATIS STREET, 1ST FLOOR | | WEST PALM BEACH, FL 33401 | | 561-248-2703 | | [email protected] | | [email protected] |
|