2019-06-06 13:32:51 | BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| NOTE: ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| SEC. 801.3 FBC-EXISTING BUILDING. |
| |
| 1- LIFE SAFETY PLAN ON SHEET A-7: |
| |
| A) A SET OF DOUBLE DOORS IN THE CORRIDOR LEADING TO THE |
| TWO EXITS WERE ELIMINATED TO ALLOW THE OPEN OFFICE |
| #319. IT LOOKS LIKE THE COMMON PATH OF TRAVEL WILL |
| EXCEED 100 FEET AS REQUIRED BY TABLE 1006.2.1 |
| FBC-BUILDING. PROVIDE THE COMMON PATH OF TRAVEL |
| DISTANCE FROM THE MOST REMOTE POINT OF THE LAST |
| WORKSTATION ON THIS NEW OPEN OFFICE AREA #319 AND FROM |
| THE MOST REMOTE POINT OF THE NEW FILES ROOM #320. |
| |
| B) PROVIDE ALSO THE OVERALL TRAVEL DISTANCE FROM THE |
| MOST REMOTE POINT OF THE LAST WORKSTATION ON THIS NEW |
| NEW OPEN OFFICE AREA #319. AND FROM THE MOST REMOTE |
| POINT OF THE NEW FILES ROOM #320. TABLE 1017.2 |
| FBC-BUILDING. |
| |
| C) SHOW ALL THE EXITS SIGNS AS REQUIRED BY SEC. 1013.1 |
| FBC-BUILDING FOR THE NEW OFFICE LAYOUT. |
| |
| D) REVISE CODE SECTIONS AND TABLES CITED ON THE LIFE |
| SAFETY SUMMARY (SUITE #350) CHART SHOWN BELOW THE LIFE |
| SAFETY FLOOR PLAN. THEY DO NOT CORRESPOND TO THE TABLES |
| AND SECTIONS OF FBC-6TH EDITION. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. |
| PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| DRAWINGS/DOCUMENTS FOR REFERENCE. |
| |