Plan Review Notes For Permit 19050002 |
Permit Number |
19050002 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-05-20 11:37:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE NO INDICATIONS THAT THE OCCUPANCY WILL | | REMAIN OPEN AND OCCUPIED DURING | | DEMOLITION/RECONSTRUCTION PERIODS. | | | | PLEASE PROVIDE A LIFE SAFETY PLAN INDICATING THE | | MAINTENANCE/FREE AND CLEAR ACCESS OF ALL REQUIRED EXITS | | ON EACH FLOOR. | | | | | | | | 2) THERE ARE NO INDICATIONS OF EXISTING FIRE ALARM AND | | FIRE SPRINKLER SYSTEMS. | | | | THESE SYSTSM SHALL BE MAINTAINED/FULLY FUNCTIONAL AT | | ALL TIMES DURING DEMOLITION AND RECONSTRUCNTION. | | | | ALL WORK ON ANY FIRE ALARM/FIRE SPRINKLER EQUIPMENT | | SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS. | | | | PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT | | AND COMPLIANCE. | | | | | | | | 3) ALL DEMO SHEETS - UNDER THE DEMOLITION PLAN GENERAL | | NOTES, # 5 THERE IS AN INDICATION TO REFER TO FIRE | | PROTECTION DRAWINGS FOR EXTENT OF WORK. | | | | THERE IS NOT FIRE PROTECTION DRAWINGS ATTACHED. | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | | | |
|