Plan Review Notes
Plan Review Notes For Permit 19050002
Permit Number 19050002
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-05-20 11:37:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO INDICATIONS THAT THE OCCUPANCY WILL
 REMAIN OPEN AND OCCUPIED DURING
 DEMOLITION/RECONSTRUCTION PERIODS.
  
 PLEASE PROVIDE A LIFE SAFETY PLAN INDICATING THE
 MAINTENANCE/FREE AND CLEAR ACCESS OF ALL REQUIRED EXITS
 ON EACH FLOOR.
  
  
  
 2) THERE ARE NO INDICATIONS OF EXISTING FIRE ALARM AND
 FIRE SPRINKLER SYSTEMS.
  
 THESE SYSTSM SHALL BE MAINTAINED/FULLY FUNCTIONAL AT
 ALL TIMES DURING DEMOLITION AND RECONSTRUCNTION.
  
 ALL WORK ON ANY FIRE ALARM/FIRE SPRINKLER EQUIPMENT
 SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT
 AND COMPLIANCE.
  
  
  
 3) ALL DEMO SHEETS - UNDER THE DEMOLITION PLAN GENERAL
 NOTES, # 5 THERE IS AN INDICATION TO REFER TO FIRE
 PROTECTION DRAWINGS FOR EXTENT OF WORK.
  
 THERE IS NOT FIRE PROTECTION DRAWINGS ATTACHED.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  