2019-05-24 11:26:53 | ***CORRECTIONS*** |
| PETER E VALENTI |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6673 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1ST BUILDING REVIEW DENIED: |
| |
| 1. FBC B 107.2.1 PROVIDE A LIFE SAFETY PLAN INCLUDING |
| EGRESS REQUIREMENTS. |
| 2. FBC B 107.2.1 PROVIDE AN ADJUSTMENT TO PLAN DETAILS |
| AND PERMIT APPLICATION. THE APPLICATION STATES THAT |
| THIS PERMIT IS FOR INTERIOR AND EXTERIOR DEMOLITION AND |
| THE PLAN PAGES INDICATE EXTERIOR WORK IS NOT INCLUDED. |
| 3. FBC B 105. PROVIDE A SEPERATE PERMIT APPLICATION FOR |
| THE BUILDING OF DEMOED AREAS. |
| 4. FBC B 110.8 PROVIDE A THRESHOLD INSPECTOR DUE TO THE |
| NATURE OF STRUCTURAL WORK PROPSED ON PAGE ID-002, |
| KEYNOTE D02 OF SUBMITTED PLANS. PLEASE SEE THE |
| REQUIREMENTS LISTED BELOW AS PER F.S. 553.79 FOR |
| THRESHOLD BUILDINGS: |
| |
| THE FOLLOWING IS REQUIRED PRIOR TO COMMENCEMENT: |
| |
| 1. COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT |
| OF UNDERSTANDING; THIS HAS BEEN SENT VIA EMAIL TO |
| CONTRACTOR. |
| |
| 2. PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL |
| PROPOSED INSPECTORS. |
| |
| 3. ALL PLANS ARE TO INCLUDE THE THRESHOLD STATEMENT |
| REQUIRED BY FS553.79(7)(D). ALL PLANS FOR THE BUILDING |
| WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| THAT, TO THE BEST OF THE ARCHITECT?S OR ENGINEER?S |
| KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| APPLICABLE MINIMUM BUILDING CODES AND |
| THE APPLICABLE FIRESAFETY STANDARDS AS DETERMINED BY |
| THE LOCAL AUTHORITY IN ACCORDANCE WITH THIS CHAPTER 553 |
| AND CHAPTER 633. |
| |
| NOTE: |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY |
| RESULT IN NEW PLAN REVIEW COMMENTS. |
2019-05-16 09:52:17 | PLANS EXAMINER, VERIFY INTERIOR ONLY & ASSURE PERMIT |
| DESCRIPTION IS ACCURATE. IF EXTERIOR, ADD A ZONING |
| REVIEW STOP. |