Plan Review Notes
Plan Review Notes For Permit 19041498
Permit Number 19041498
Review Stop B
Sequence Number 1
Notes
Date Text
2019-05-08 07:44:452017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19041498
 ADD: 400 N. FLAGLER DR. / SUITE: 1201
 CONT: COUNIHAN CONSTRUCTION LLC
 TEL: 561-722-6255
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MAY 08/ 2019
 ACTION: DENIED
  
 1) THE SUBMITTED PLANS INDICATE THE REPLACEMENT OF
 COMPONENTS AND CLADDING, WINDOWS AND DOORS. PARTIAL
 WIND DESIGN CRITERIA WAS PROVIDED FOR THIS REVIEW.
 PLEASE SHOW CODE COMPLIANCE WITH:
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1.1. COMPLIED. ULTIMATE DESIGN WIND SPEED, VULT,
 (3-SECOND GUST), MILES PER HOUR AND NOMINAL DESIGN WIND
 SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 1.2. COMPLIED. RISK CATEGORY.
  
 1.3.COMPLIED. WIND EXPOSURE. APPLICABLE WIND DIRECTION
 IF MORE THAN ONE WIND EXPOSURE IS UTILIZED. TABLE
 1609.7.2. HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
  
 1.4. COMPLIED. APPLICABLE INTERNAL PRESSURE
 COEFFICIENT.
  
 1.5. NOT COMPLIED. DESIGN WIND PRESSURES TO BE USED FOR
 EXTERIOR COMPONENTS AND CLADDING MATERIALS SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
 SHEET A2 HAS +63.3/-84.7 PRESSURES FOR WINDOWS AND S.
 G. DOORS WORST CASE! THAT WOULD BE ZONE 5 AT 10 SQ. FT.
 FOR 250 MEAN ROOF HEIGHT/ EXPOSURE D THE PRESSURES ARE
 +68.5/ -125.5 PSF. PRESSURES TAKEN FROM FRANK BENNARDO
 P. E. EXPRESS ENGINEERING CALCULATION SHEET WIND AT 170
 MPH EXPOSURE D AND MEAN ROOF HEIGHT> 60 FEET. PLEASE
 SUBMIT HOW YOUR PRESSURES WERE DERIVED?
  
 2) PLEASE NOTE THAT THERE WERE ONLY ONE SET OF EACH OF
 THESE DOCUMENTS (PRODUCT APPROVALS):
  
 2A) NOA: 17-1218.21 EGS INTERNATIONAL. ATLANTIC
 ALUMINUM SLIDING GLASS DOORS- S. M. I.
  
 2B)NOA:17-0630.04 PGT SERIES?SH-800 ALUMINUM SINGLE
 HUNG WINDOWS- S. M. I.
  
 2C) (2) SETS OF ALL DOCUMENTS ARE REQUIRED FOR REVIEW,
 ONE SET FOR RECORD RETENTION, THE OTHER FOR THE FIELD
 INSPECTOR. 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION107.1.
  
 2D) NOA: 17-1218.21 EGS INTERNATIONAL. ATLANTIC
 ALUMINUM SLIDING GLASS DOORS- S. M. I., PLEASE NOTE FOR
 THIS PRODUCT ALL AREAS OF INTEREST WERE CIRCLED IN THIS
 NOA WITH THE EXCEPTION OF SILL HEIGHTS FOUND ON SHEET 2
 OF 8. SILL HEIGHTS ARE THE LIMITING FACTOR FOR THE
 EXTERIOR (+) PRESSURES. PLEASE CIRCLE WHICH SILL IS TO
 BE INSTALLED IN THE 2ND SET OF APPROVALS TO BE
 SUBMITTED. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2E) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2F) SHEET A2 THERE MAYBE A DISCREPANCY OR TYPO IN THE
 TYPE OF WINDOW TO BE INSTALLED IN THE LIVING AREA. THE
 PLAN INDICATES INSTALL NEW H. S. WINDOWS. IS H. S.
 WINDOWS HORIZONTAL SLIDERS? THE CONTRACTOR SUBMITTED
 PGT SERIES SH-800 ALUMINUM SINGLE HUNG WINDOWS.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) SHEET A1 OF THE PLANS INDICATES FLOOR COVERINGS ARE
 TO BE REMOVED AS PER PLAN. SHEET A2 ALSO INDICATES NEW
 FLOOR COVERINGS ARE TBD/ TO BE DETERMINED, COORDINATE
 WITH OWNER. THIS WILL CONSTITUTE A REVISION SINCE THE
 TYPE OF MATERIAL TO BE INSTALLED IS UNKNOWN. THERE ARE
 3 CODE SECTIONS THAT WILL NEED TO SHOW COMPLIANCE FOR
 SOUND, STRUCTURE BORNE SOUND, AIR BORNE SOUND AND FLAME
 SPREAD.
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 3B) FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 3C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved