2019-05-08 07:44:45 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19041498 |
| ADD: 400 N. FLAGLER DR. / SUITE: 1201 |
| CONT: COUNIHAN CONSTRUCTION LLC |
| TEL: 561-722-6255 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. MAY 08/ 2019 |
| ACTION: DENIED |
| |
| 1) THE SUBMITTED PLANS INDICATE THE REPLACEMENT OF |
| COMPONENTS AND CLADDING, WINDOWS AND DOORS. PARTIAL |
| WIND DESIGN CRITERIA WAS PROVIDED FOR THIS REVIEW. |
| PLEASE SHOW CODE COMPLIANCE WITH: |
| 2017 FBC-B 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| |
| 1.1. COMPLIED. ULTIMATE DESIGN WIND SPEED, VULT, |
| (3-SECOND GUST), MILES PER HOUR AND NOMINAL DESIGN WIND |
| SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| 1609.3.1. |
| |
| 1.2. COMPLIED. RISK CATEGORY. |
| |
| 1.3.COMPLIED. WIND EXPOSURE. APPLICABLE WIND DIRECTION |
| IF MORE THAN ONE WIND EXPOSURE IS UTILIZED. TABLE |
| 1609.7.2. HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1. |
| |
| 1.4. COMPLIED. APPLICABLE INTERNAL PRESSURE |
| COEFFICIENT. |
| |
| 1.5. NOT COMPLIED. DESIGN WIND PRESSURES TO BE USED FOR |
| EXTERIOR COMPONENTS AND CLADDING MATERIALS SPECIFICALLY |
| DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| SHEET A2 HAS +63.3/-84.7 PRESSURES FOR WINDOWS AND S. |
| G. DOORS WORST CASE! THAT WOULD BE ZONE 5 AT 10 SQ. FT. |
| FOR 250 MEAN ROOF HEIGHT/ EXPOSURE D THE PRESSURES ARE |
| +68.5/ -125.5 PSF. PRESSURES TAKEN FROM FRANK BENNARDO |
| P. E. EXPRESS ENGINEERING CALCULATION SHEET WIND AT 170 |
| MPH EXPOSURE D AND MEAN ROOF HEIGHT> 60 FEET. PLEASE |
| SUBMIT HOW YOUR PRESSURES WERE DERIVED? |
| |
| 2) PLEASE NOTE THAT THERE WERE ONLY ONE SET OF EACH OF |
| THESE DOCUMENTS (PRODUCT APPROVALS): |
| |
| 2A) NOA: 17-1218.21 EGS INTERNATIONAL. ATLANTIC |
| ALUMINUM SLIDING GLASS DOORS- S. M. I. |
| |
| 2B)NOA:17-0630.04 PGT SERIES?SH-800 ALUMINUM SINGLE |
| HUNG WINDOWS- S. M. I. |
| |
| 2C) (2) SETS OF ALL DOCUMENTS ARE REQUIRED FOR REVIEW, |
| ONE SET FOR RECORD RETENTION, THE OTHER FOR THE FIELD |
| INSPECTOR. 2017 WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION107.1. |
| |
| 2D) NOA: 17-1218.21 EGS INTERNATIONAL. ATLANTIC |
| ALUMINUM SLIDING GLASS DOORS- S. M. I., PLEASE NOTE FOR |
| THIS PRODUCT ALL AREAS OF INTEREST WERE CIRCLED IN THIS |
| NOA WITH THE EXCEPTION OF SILL HEIGHTS FOUND ON SHEET 2 |
| OF 8. SILL HEIGHTS ARE THE LIMITING FACTOR FOR THE |
| EXTERIOR (+) PRESSURES. PLEASE CIRCLE WHICH SILL IS TO |
| BE INSTALLED IN THE 2ND SET OF APPROVALS TO BE |
| SUBMITTED. 107.2.1.2. ADDITIONAL INFORMATION IS |
| REQUIRED. |
| |
| 2E) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 2F) SHEET A2 THERE MAYBE A DISCREPANCY OR TYPO IN THE |
| TYPE OF WINDOW TO BE INSTALLED IN THE LIVING AREA. THE |
| PLAN INDICATES INSTALL NEW H. S. WINDOWS. IS H. S. |
| WINDOWS HORIZONTAL SLIDERS? THE CONTRACTOR SUBMITTED |
| PGT SERIES SH-800 ALUMINUM SINGLE HUNG WINDOWS. |
| 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 3) SHEET A1 OF THE PLANS INDICATES FLOOR COVERINGS ARE |
| TO BE REMOVED AS PER PLAN. SHEET A2 ALSO INDICATES NEW |
| FLOOR COVERINGS ARE TBD/ TO BE DETERMINED, COORDINATE |
| WITH OWNER. THIS WILL CONSTITUTE A REVISION SINCE THE |
| TYPE OF MATERIAL TO BE INSTALLED IS UNKNOWN. THERE ARE |
| 3 CODE SECTIONS THAT WILL NEED TO SHOW COMPLIANCE FOR |
| SOUND, STRUCTURE BORNE SOUND, AIR BORNE SOUND AND FLAME |
| SPREAD. |
| |
| BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| 2017) |
| FOR TILE, STONE, MARBLE, AND WOOD FLOORING ALL NEED TO |
| HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES |
| TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| |
| 3A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 3B) FBC-B 2017 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| 3C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |