Plan Review Notes
Plan Review Notes For Permit 19041484
Permit Number 19041484
Review Stop G
Sequence Number 1
Notes
Date Text
2019-05-01 16:50:31GAS 1ST REVIEW**DENIED**
  
  
 1) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
  
 2) THE SIZING CHART YOU REFERANCE 402.4 (5) IS A 2LB
 WITH 1 POUND PRESSURE DROP LEAVING 27.67 IN W.C.. THIS
 IS ALMOST 3 TIMES MORE THEN THE DESIGNED PREESURE OF
 THE TANKLESS. PLEASE CLARIFY. FBC 107.2.1
  
 3) YOUR PLAN LIST INCOMING PRESSURE AS 10 PSI. SUBMIT
 MANUFACTURER?S SPECIFICATIONS FOR BOTH 1ST AND 2ND
 STAGEOF THE PRESSURE REGULATORS. REGULATORS INSTALLED
 ON THE EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR
 OUTDOOR INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES.
 SEC. G2421.1.
  
 4) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
  
 5) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS
 REPLACING AN EXISTING TANKLESS WATER HEATER OR IS IT
 REPLACING A STORAGE TANK TYPE WATER HEATER OR IS IT
 BEING ADDED TO THE EXISTING HOT WATER SYSTEM? INDICATE
 ON THE APPLICATION IN THE DESCRIPTION OF WORK.
  
 6) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 7) . A RISER ISOMETRIC IS REQUIRED. PLEASE SHOW SHUTOFF
 VALVE AND DRIP LEG. FBC 107.3.5
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR