Plan Review Notes For Permit 19041480 |
Permit Number |
19041480 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-05-09 10:55:04 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | 1) THERE ARE NO INDICATIONS OF FIRE DEPARTMENT | | ACCESS/GATES. A 20' FIRE LANE ACCESS WIDTH IS REQUIRED | | FOR SITE ACCESS. | | | | PER NFPA 1 | | | | 18.2.3 FIRE DEPARTMENT ACCESS ROADS. | | 18.2.3.1 REQUIRED ACCESS. | | 18.2.3.1.1 APPROVED FIRE DEPARTMENT ACCESS ROADS SHALL | | BE PROVIDED | | FOR EVERY FACILITY, BUILDING, OR PORTION OF A BUILDING | | HEREAFTER | | CONSTRUCTED OR RELOCATED. | | 18.2.3.1.2 FIRE DEPARTMENT ACCESS ROADS SHALL CONSIST | | OF ROADWAYS, FIRE | | LANES, PARKING LOT LANES, OR A COMBINATION THEREOF. | | | | 18.2.3.4.1 DIMENSIONS. | | 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN | | UNOBSTRUCTED | | WIDTH OF NOT LESS THAN 20 FT (6.1 M). | | | | | | PLEASE REVIEW AND PROVIDE LOCATION(S) | | | | | | 2) IT IS HIGHLY RECOMMENDED THAT THESE GATES BE | | PROVIDED WITH A KNOX PADLOCK FOR EMERGENCY INCIDENT | | ACCESS SHOULD THE GATE BE LOCAKED AT ANY TIME. | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | | | |
|