Plan Review Notes
Plan Review Notes For Permit 19041466
Permit Number 19041466
Review Stop E
Sequence Number 1
Notes
Date Text
2019-05-02 07:20:40ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION (FAULT
 CURRENT) FOR BOTH 600AMP SERVICES INCLUDING INFORMATION
 OF SHORT CIRCUIT CURRENT FROM POWER COMPANY. NEC 110.9,
 110.10
  
 2. PROVIDE LOCATION OF TRANSFORMER AND APPROX DISTANCE
 AWAY FROM SERVICE. FBC 107.2.1
  
 3. IF YOU WISH TO DE-RATE GROUNDED CONDUCTOR (NEUTRAL)
 PROVIDE LOAD CALCULATION FOR NEUTRAL SHOWING MAXIMUN
 UNBALANCED LOAD NEUTRAL COULD BE EXPOSED TO. FBC
 107.2.1 NEC 220
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
  