2019-05-02 07:20:40 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION (FAULT |
| CURRENT) FOR BOTH 600AMP SERVICES INCLUDING INFORMATION |
| OF SHORT CIRCUIT CURRENT FROM POWER COMPANY. NEC 110.9, |
| 110.10 |
| |
| 2. PROVIDE LOCATION OF TRANSFORMER AND APPROX DISTANCE |
| AWAY FROM SERVICE. FBC 107.2.1 |
| |
| 3. IF YOU WISH TO DE-RATE GROUNDED CONDUCTOR (NEUTRAL) |
| PROVIDE LOAD CALCULATION FOR NEUTRAL SHOWING MAXIMUN |
| UNBALANCED LOAD NEUTRAL COULD BE EXPOSED TO. FBC |
| 107.2.1 NEC 220 |
| |
| END OF COMMENTS. |
| |