Plan Review Notes
Plan Review Notes For Permit 19041454
Permit Number 19041454
Review Stop G
Sequence Number 2
Notes
Date Text
2020-01-22 10:45:351) THE GAS RISER SHOWS A DISTANCE OF 150 FEET FROM THE
 GAS METER TO THE GENERATOR. ON THE GAS SIZING TABLE FOR
 THE METALLIC PIPING THE 150 FEET ROW IS HIGHLIGHTED BUT
 ON THE PE SIZING TABLE THE 80 FEET ROW IS HIGHLIGHTED.
 WHERE ARE YOU GETTING THIS 80 FEET FROM? THE 150 FEET
 ROW MUST BE USED FOR SIZING OF THE GAS SYSTEM. 2017
 FBC-FUEL GAS SEC.402.4.1.
 2) THE GAS RISER AND GENERATOR SPECIFICATIONS CALL OUT
 THE BTU LOAD OF THE GENERATOR AS OVER ONE MILLION BTU'S
 YET THE SIZING TABLES FOR THE PE AND METALLIC PIPING AT
 150 FEET CAN ONLY CARRY 860 BTU'S AND 751 BTU'S
 RESPECTIVELY. CLARIFY. WPB AMEND.TO FBC SEC. 107.2.1,
 TABLES 402.4 (5), 402.4(22).
 3) SUBMIT TWO COPIES OF THE SIZING TABLE FOR THE LOW
 PRESSURE SYSTEM.WPB AMEND. TO FBC SEC. 107.2.1, 2017
 FBC-FUEL GAS SEC.402.3.
 4) WHERE CONNECTED TO RIDGID PIPING, A UNION SHALL BE
 INSTALLED WITHIN ONE FOOT OF EITHER SIDE OF THE MP
 REGULAROR. 410.2 (7).
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MP
 REGULATOR. REGULAOTRS SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION.
 6) IDENTIFY ON THE REGULATOR SPECIFICATIONS WHICH
 REGULATOR MODEL IS BEING INSTALLED. THE REGULATOR SHALL
 BE CAPABLE OF HANDLING THE BTU LOAD OF THE APPLIANCE OR
 THE THE EQUIPMENT. 2017 FBC-FUEL GAS SEC.410.2 (3).
 7) CITY RECORDS SHOW THAT THERE IS AN EXISTING GAS
 WATER HEATER AT THIS LOCATION. THE BTU LOAD OF THE
 EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU
 LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS
 PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST
 BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A
 GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF
 EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE
 PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. FGC SECS. 401.4, 401.8, 402.1, 402.2,
 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, G2413.2,
 G2413.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  