Plan Review Notes For Permit 19041454 |
Permit Number |
19041454 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-05-02 13:51:43 | GAS 1ST REVIEW**DENIED**EMAILED TOYA TO DISCUSS | | | | I AM NOT ABLE TO PERFORM A THOROUGH REVIEW AT THIS | | TIME. YOUR PLAN LIST INSTALLATION MANUALS/ | | SPECIFICATION FOR FOR 3 DIFFERENT KW GENERATORS AND 1 | | DIESEL 80 KW ( 60,70,80, 80 DIESEL) YOUR GAS ISOMETRIC | | SHOWS 60KW 925BTU'S WITH 150' 3/4 P.E BUT SIZING CHART | | PROVIDED IS HIGHLIGHT @ 80' AND THE 2ND SIZING CHART | | PROVIDED IS 2LB SCH 40 PIPE HIGHLIGHTED @ 150' BUT NO | | METAL PIPE IS SHOWN ON PLAN | | | | | | TIM HUNT | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | BUILDING DIVISION | | CITY OF WEST PALM BEACH | | 401 CLEMATIS STREET, 1ST FLOOR | | WEST PALM BEACH, FL 33401 | | 561-248-2703 | | [email protected] | | [email protected] | | |
|