2019-06-05 10:33:42 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE NO INDICATIONS OF WHAT THIS GENERATOR WILL | | PROVIDE POWER TO; THE ENTIRE BUILDING, INCLUDING ALL | | LIFE SAFETY EQUIPMENT AND SYSTEMS? | | | | PLEASE PROVIDE A DESCRIPTION OF POWER SERVICE | | | | | | 1A) THERE ARE NO INDICATIONS OF COMPLIANCE WITH ANY | | FIRE PREVENTION CODE. | | | | THE INSTALL SHALL COMPLY WITH NFPA 37 STANDARD FOR THE | | INSTALLATION AND USE OF STATIONARY COMBUSTION ENGINES | | AND GAS TURBINES 2015 EDITION AND NFPA 110 STANDARD FOR | | EMERGENCY AND STANDBY POWER SYSTEMS2013 EDITION | | | | PLEASE REVIEW , ENSURE COMPLIANCE AND PROVIDE AN | | APPLICABLE NOTE. | | | | | | | | 2) THERE IS INSUFFICIENT DETAIL INDICATED FOR THE | | LOCATION, BOTH DIMENSIONS FROM THE BUILDING AND ALSO | | FROM WALL OPENINGS. | | | | PLEASE PROVIDE SPECIFIC DETAILS, LOCATIONS AND | | DIMENSIONS. | | | | | | 3) THERE ARE NO INDICATIONS OF THE FOUNDATION AND/OR | | HOLD DOWN DETAILS | | | | PLEASE PROVIDE DETAILS. | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | | | | | | | | | |
|