2019-05-16 10:48:09 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | 600 KCMIL CAN NOT FEED A 600A BREAKER OR SWITCH | | TRANSFRER SWITCH | | | | 600 KCMIL CAN NOT FEED A 400A BREAKER IN THE MAIN | | | | ANOTHER PAGE SHOWS 400 KCMIL WIRE PLEASE CHECK RISER | | DIAGRAM FOR MISTAKES |
|