Plan Review Notes For Permit 19041453 |
Permit Number |
19041453 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-05-03 17:08:44 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #19041453 | | 5/3/19 | | | | CODES IN EFFECT: | | | | | | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET M-1: THE RETRUN TRANSFER DUCTS FROM BEDROOMS | | 1, 2, & 3 ARE UNDERSIZED PER SECTION M1602.3 FBC R. THE | | TRANSFER DUCTS SHALL BE SIZED 1-1/2 TIMES THE CROSS | | SECTIONAL AREA OF THE SUPPLY DUCT ENTERING THE ROOM. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|