2019-05-08 07:59:55 | 1ST REVIEW: 19041429 |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| GAS COMMENTS: |
| |
| 1. THE GAS DRAWING WAS ORIGINALLY PART OF A MASTER SET |
| OF PLANS DESIGNED BY AN ENGINEER THE REVISION SHALL BE |
| SIGNED AND SEALED BY ORIGINAL ENGINEER. PER WPB AMEND |
| TO FBC 107.2.1 |
| |
| 2. LABEL ALL PIPING ON RISER EHD IS SHOWN ON SOME OF |
| THE PIPING IS THIS CSST TYPE PLEASE CLARIFY. PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| 3. SIZE AND SHOW LENGTH OF PIPING BETWEEN REGULATOR AND |
| APPLIANCE ALSO SHOW REQUIRED DRIP LEG. PER FBC RES |
| G2419.4 AND WPB AMEND TO FBC 107.2.1 |
| |
| 4. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| FBC-FUEL GAS CODE SEC.304.1, 614.6 OR 2017 FBC-RES. |
| SEC.G 2407.1 AND G2439.4 |
| |
| 5. FOR THE FIRE PLACE SUBMIT TWO COPIES OF A DETAIL |
| SHOWING THE TYPE OF VENT, LOCATION, SIZE, TERMINATION |
| POINT, HEIGHT ABOVE THE ROOF AND ANCHORING DETAILS OF |
| THE GAS VENT(S) PER 2017 FBC-FUEL GAS SECS. 502 THRU |
| 505 OR 2017 FBC-RES. SEC.G2426 THROUGH G2439. |
| |
| 6. PROVIDE A FLOOR PLAN THAT IDENTITY'S EACH ROOM SHALL |
| COMPLY WITH FBC RES G2406.2 |
| |
| 7. THE FIRE LOG SYSTEM SHALL COMPLY WITH FBC RES |
| G2433.1 THE MANUFACTURE SPECS THAT WERE PROVIDED DID |
| NOT SHOW THIS, LOG LIGHTERS SHALL BE TESTED IN |
| ACCORDANCE WITH CSA 8 |
| |
| 8. PROVIDE MANUFACTURE SPEC FOR THE FIRE PLACE |
| ENCLOSURE AND COOK TOP, THE SPECS PROVIDED WERE JUST |
| FOR LOG BURNER.PER WPB AMEND TO FBC 107.2.1 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |