2019-05-01 15:26:36 | PLUMBING 1ST REVIEW**DENIED** | | | | 1) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE | | MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM | | ITS PUMP CURVE AND THE SIMPLIFIED TOTAL DYNAMIC HEAD | | CALCULATION IS NO LONGER ALLOWED TO BE USED IN | | DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC | | 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 EDITION | | ADDRESSES FLOW RATE IN GALLONS PER MINUTE (GPM). IT | | REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED | | THE LISTED MAXIMUM FLOW RATE OF THE SUCTION OUTLET | | FITTING ASSEMBLY (DRAIN COVER).THE TDH CALCULATIONS | | MUST INCLUDE ALL OF THE SYSTEM COMPONENTS INCLUDING | | SUCTION AND RETURN PIPING, FITTINGS, VALVES, HEATER, | | FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS EXCEPT | | THE PUMP. | | | | 2) IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS | | SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL. THIS | | IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE | | TDH CALCULATIONS. ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, | | 4.4.9.1 | | | | TIM HUNT | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | BUILDING DIVISION | | CITY OF WEST PALM BEACH | | 401 CLEMATIS STREET, 1ST FLOOR | | WEST PALM BEACH, FL 33401 | | 561-248-2703 | | [email protected] | | [email protected] | | | | | | | | | | | | | | |
|