2019-04-26 12:13:01 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1- ONLY ONE COPY OF PRODUCT APPROVALS WAS SUBMITTED. |
| PROVIDE 2 COPIES OF ALL PRODUCT APPROVALS AS REQUIRED |
| BY SEC. 107.1 CITY AMENDMENTS. |
| |
| 2- ROOFF TILE NOA 18-0829.03 SUBMITTED: |
| CLEARLY MARK ROOF TILE FASTENING METHOD AS REQUIRED BY |
| CITY POLICY FOR ALL ROOFING PERMITS. |
| NOTE: THERE IS A LIGHT MARK NEXT TO THE THE TWO PATTY |
| ADHESIVE SET SYSTEM #5 ON PAGE 5 OF 7 OF NOA SUBMITTED. |
| THE MINIMUM ATTACHMENT RESISTANCE FOR TWO PATTY |
| ADHESIVE SET #5 IS 26.1. IF THIS IS THE PADDY SIZE TO |
| BE INSTALLED, THEN IT DOESN'T SEEM TO COMPLY WITH THE |
| ATTACHMENT RESISTANCE REQUIRED BY SEC. 2.5 OF RAS 127. |
| CLEARLY MARK ANOTHER ADHESIVE SET SYSTEM THAT PROVIDES |
| ENOUGH ATTACHMENT RESISTANCE OR PROVIDE COMPLETE |
| CALCULATIONS SHOWING THAT THE SELECTED SYSTEM WORKS. |
| |
| 3- ROOF TILE ADHESIVE NOA SUBMITTED. CLEARLY MARK |
| ADHESIVE PLACEMENT THAT CORRESPONDS TO REVISED PADDY |
| SIZE REQUIRED ON ITEM #2 ABOVE. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |