2019-04-26 09:48:21 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1- ACCORDING TO PALM BEACH COUNTY PROPERTY APPRAISER, |
| THE VALUE OF THE STRUCTURE IS $319,214. THEREFORE, |
| NEEDS TO COMPLY WITH THE ROOF TO WALL CONNECTIONS AS |
| REQUIRED BY SEC. 706.8 FBC-EXISTING BUILDING. SHOW |
| COMPLIANCE. NOTE: A SEPARATE SUB-PERMIT IS REQUIRED FOR |
| ROOF TO WALL CONNECTIONS. THIS WORK CAN NOT BE DONE BY |
| THE ROOFING CONTRACTOR UNLESS ROOFING CONTRACTOR |
| POSSESSES THE PROPER LICENSE TO PERFORM THIS WORK. |
| |
| 2- ENGINEERING SUBMITTED FOR FLAT ROOF: |
| A) ENGINEER TO REVISE THE SPACING OF THE SIDE LAPS. IT |
| DOESN'T MATCH THE SPACING SHOWN ON THE SYSTEM #W-14 OF |
| FLORIDA PRODUCT APPROVAL FL11475-R8 SUBMITTED. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| B) ENGINEER TO REVISE THE FASTENER SPACING SPECIFIED |
| FOR ROOF ZONE #3. ACCORDING TO SEC. 8.1 OF RAS 117 "THE |
| MINIMUM FASTENER SEPARATION SHALL NOT BE LESS THAN 4 |
| IN. O.C.". REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| C) RAS 117 CALCULATIONS SUBMITTED HAVE A COPY OF A |
| DIGITAL SIGNATURE. THIS IS NOT A DIGITAL SUBMITTAL. |
| CALCULATIONS NEED TO HAVE THE ORIGINAL SEAL AND |
| SIGNATURE OF THE ENGINEER OF RECORD AS REQUIRED BY SEC. |
| 61G15-23.003 FAC AND CHAPTER 471 F.S. WHEN SUBMITTING |
| PLANS/DOCUMENTS FOR PUBLIC RECORDS. |
| |
| 3- ROOF TILE NOA 18-0119.03 SUBMITTED: CLEARLY MARK |
| ROOF TILE FASTENING METHOD AS REQUIRED BY CITY POLICY |
| FOR ALL ROOFING PERMITS. |
| |
| 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR ROOF TILE ADHESIVE. |
| |
| 5-- ROOFING UNDERLAYMENT FLORIDA PRODUCT APPROVALS |
| FL14317-R10 SUBMITTED: |
| A) CLEARLY MARK WHICH MAXIMUM DESIGN PRESSURES ASSEMBLY |
| FORM SEC. 5.6.4 OF PRODUCT APPROVAL IS GOING TO BE |
| USED. OR IF USING THE FRSA/TRI APRIL 2012 (04-12) |
| REVISED EDITION, THEN PROVIDE COMPLETE INFORMATION |
| SHOWING THE DETERMINATION OF DESIGN WIND LOADS AS |
| REQUIRED BY SEC. 5.6.4. |
| |
| 6- SPECIFY ROOF PITCH, BUILDING MEAN HEIGHT AS REQUIRED |
| BY CITY POLICY FOR ALL ROOFING PERMITS AND SEC. |
| 107.02.1 CITY AMENDMENTS. |
| |
| 7- THERE IS MORE THAN ONE STRUCTURE IN THIS PROPERTY. |
| PROVIDE MAP OR SKETCH SHOWING LOCATION OF AREA OF WORK |
| AND SQUARE FOOTAGE OF EACH AREA (PITCH AND FLAT) AS |
| REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS AND |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |