2019-05-14 19:11:06 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) DOOR 110 FOR THE NEW IT/ELECTRICAL ROOM IS NOT | | LISTED IN THE DOOR SCHEDULE ON SHEET A2.1.1. | | | | 2) THE REVISION IS TO ADD AN IT/ELECTRICAL ROOM TO THE | | BUSINESS OCCUPANCY. FBC TABLE 509 FOR INCIDENTIAL USES | | REQUIRES A ONE HOUR FIRE SEPARATION IF THERE IS | | STATIONARY STORAGE BATTERY SYSTEMS HAVING A LIQUID | | ELECTROLYTE CAPACITY OF MORE THAN 50 GALLONS FOR | | FLOODED LEAD-ACID, NICKEL CADIUM OR VRLA, OR MORE THAN | | 1,000 POUNDS FOR LITHIUM-ION AND LITHIUM METAL POLYMER | | USED FOR FACILITY STANDBY POWER, EMERGENCY POWER OR | | UNINTERRUPTABLE POWER SUPPLIES. PLEASE ADVISE. FBC | | 509.4. | | | | 3) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. |
|