Plan Review Notes For Permit 19041286 |
Permit Number |
19041286 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-05-03 07:50:29 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. DETAIL 4-AE107, PROVIDE DETAILS FOR THE FIRE RATED | | ASSEMBLIES AS THIS IS REQUIRED FOR INSPECTIONS. I WAS | | NOT ABLE TO LOCATE GA FC 5406 OR RC 2601 FOR METAL | | FRAMING (FOUND DETAILS FOR WOOD), FBC 107. | | | | 2. REVISE PLAN TO CLARIFY WHY THE SOFFIT IS RATED, WHAT | | TYPE OF RATED WALL THIS IS (PARTITION, BARRIER, ETC) | | FBC B CHAPTER 7 AND WHY IT IS REQUIRED TO BE RATED | | (OCCUPANCY SEPARATION, ATRIUM, FIRE AREAS, OTHER | | REQUIREMENT?). | | | | 3. PLEASE NOTE THAT THE MASTER PERMIT INDEX REFERS TO | | MANY ARCHITECTURAL PAGES WHICH WERE NOT SUBMITTED. | | MASTER PERMIT 18060261 SHEET 004 WHICH IS LS100 (NOT | | NAMED PROPERLY IN PROJECTDOX) APPEARS TO DEPICT A TWO | | HOUR RATED WALL IN THIS LOCATION. DETAIL 1-004.04 AE101 | | DOES NOT SHOW CONTINUITY FOR THE RATED WALL. | | |
|