Plan Review Notes
Plan Review Notes For Permit 19041286
Permit Number 19041286
Review Stop B
Sequence Number 1
Notes
Date Text
2019-05-03 07:50:29****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. DETAIL 4-AE107, PROVIDE DETAILS FOR THE FIRE RATED
 ASSEMBLIES AS THIS IS REQUIRED FOR INSPECTIONS. I WAS
 NOT ABLE TO LOCATE GA FC 5406 OR RC 2601 FOR METAL
 FRAMING (FOUND DETAILS FOR WOOD), FBC 107.
  
 2. REVISE PLAN TO CLARIFY WHY THE SOFFIT IS RATED, WHAT
 TYPE OF RATED WALL THIS IS (PARTITION, BARRIER, ETC)
 FBC B CHAPTER 7 AND WHY IT IS REQUIRED TO BE RATED
 (OCCUPANCY SEPARATION, ATRIUM, FIRE AREAS, OTHER
 REQUIREMENT?).
  
 3. PLEASE NOTE THAT THE MASTER PERMIT INDEX REFERS TO
 MANY ARCHITECTURAL PAGES WHICH WERE NOT SUBMITTED.
 MASTER PERMIT 18060261 SHEET 004 WHICH IS LS100 (NOT
 NAMED PROPERLY IN PROJECTDOX) APPEARS TO DEPICT A TWO
 HOUR RATED WALL IN THIS LOCATION. DETAIL 1-004.04 AE101
 DOES NOT SHOW CONTINUITY FOR THE RATED WALL.
  