Plan Review Notes
Plan Review Notes For Permit 19041261
Permit Number 19041261
Review Stop M
Sequence Number 1
Notes
Date Text
2019-05-06 12:18:241ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19041261
 5/6/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE NOTE THERE ARE NO WPB BUILDING DEPARTMENT
 RECORDS OF LEGALLY PERMITTED AC SYSTEMS BEING INSTALLED
 AT THE APARTMENTS. REFER TO SECTION C503.2 FBC EC- FULL
 COMPLIANCE WITH THE ENERGY CODE IS REQUIRED, WHICH
 MEANS THAT THE FORM R402 MUST BE COMPLETELY FILLED OUT
 AND THREE PAGES ARE MISSING. PLEASE REVIEW THE "SCOPE"
 OF THE FORM LISTED IN THE TOP PRAGRAPH. IN ADDITION,
 PLEASE NOTE THAT THE ENERGY FORM R402 AND THE AC
 CALCULATIONS MUST BE SIGNED BY THE PERSON WHO PREPARED
 THE FORM AND THE OWNER/AGENT- SECTION R103.1.1.2 FBC
 EC.
  
 2) SHEET M/P1: PROVIDE AC DUCT LAYOUT PLANS SHOWING
 DUCT RUNS, DUCT SIZES, AND RETURNS. PLEASE NOTE THAT
 ALTHOUGH THE PLAN IS INDICATING EXISTING DUCTWORK,
 THERE ARE NO WPB BUILDING DEPARTMENT RECORDS OF ANY
 PRIOR DUCT INSTALLATIONS- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  