Plan Review Notes For Permit 19041261 |
Permit Number |
19041261 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-05-16 14:10:05 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) SHEET CVR - THERE NO INDICATIONS OF COMPLIANCE WITH | | ANY FIRE CODE. | | | | THE PROPOSED PROJECTS SHALL MEET THE REQUIREMENTS OF | | THE 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH | | INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101. | | | | SPECIFICALLY, CH 31 EXISTING APARTMENT OCCUANCIES. | | | | PLEASE REVIEW NAD ENSURE COMPLIANCE AND PROVIDE AN | | APPLICABLE NOTE OF CODE REFERENCE. | | | | | | | | | | 2) SHEET A 1 - THE ARE REFERENCES TO EXISTING PARTY | | WALLS BETWEEN EACH UNIT(S). | | | | DO THESE PARTY WALLS HAVE A FIRE RATING? DO THEY GO ALL | | THE WAY TO THE UNDER SIDE OF THE ROOF SHEATHING? | | | | PLEASE PROVIDE DETAILS. | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] |
|