2019-05-16 14:01:39 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY |
| SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| INTERSYSTEM BONDING TERMINATION POINT. ARE PANELS BEING |
| REPLACED MAIN BREAKER OR MAIN LUG TYPE PANELS? PROVIDE |
| CLARIFICATIONS. NEC 215.5, 230, 250.50, 250.94, 408.30 |
| 2. KITCHENS REQUIRE A MINUMUM OF TWO SMALL APPLIANCE |
| BRANCH CIRCUITS. PROVIDE CORRECTION. NEC 210.11(C)(1) |
| 3. PROVIDE ACCURATE LOAD CALCULATION. A MINUMUM OF TWO |
| SMALL APPLIANCE BRANCH CIRCUITS ARE REQUIRED. NEC 220 |
| 4. PANEL SCHEDULE FOR UNITS STATE THAT THE ELECTRICAL |
| SERVICE IS 120/208 VOLT. LOAD CALCULATION STATES THE |
| SERVICE IS 120/240 VOLT. CORRECT DISCREPANCY. WPB FBC |
| 107.2.1 |
| 5. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| NOTE WILL SUFFICE. NEC 406.12 |
| 6. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS |
| INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES. |
| SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION. |
| PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902; |
| FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE. |
| 7. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR |
| SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE |
| EQUIPMENT PER CODE. NEC 210.63 |
| 8. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS |
| IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC |
| 109.3 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |