2019-05-06 14:31:582017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19041261
 ADD: 415 50TH ST. / BUILDING #3 / (3) DWELLING UNITS
 CONT: PREMIER BUILDERS & DEVELOPMENT
 TEL: 561-891-1607
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MAY MON. 06/2019
 ACTION: DENIED
  
 1) THE COVERSHEET THE DESIGNER OF RECORD HAS NOT
 INDICATED AS TO WHICH METHOD THE PLANS WERE DEVELOPED
 UNDER THE 2017 FBC-EXISTING BUILDING CODE, SEE SECTION
 301.1. THE REPAIR, ALTERATION, CHANGE OF OCCUPANCY,
 ADDITION OR RELOCATION OF ALL EXISTING BUILDINGS SHALL
 COMPLY WITH ONE OF THE METHODS LISTED IN SECTIONS
 301.1.1 THROUGH 301.1.3 AS SELECTED BY THE APPLICANT.
 SECTIONS 301.1.1 THROUGH 301.1.3 SHALL NOT BE APPLIED
 IN COMBINATION WITH EACH OTHER.
  
 301.1.1 PRESCRIPTIVE COMPLIANCE METHOD.
  
 301.1.2 WORK AREA COMPLIANCE METHOD.
  
 301.1.3 PERFORMANCE COMPLIANCE METHOD.
  
 2) SHEET A1 :
  
 2A) UNDER THE HEADING OF GENERAL NOTE # 07 THE PLAN
 INDICATES WINDOW AND DOORS ARE TO BE REPLACED UNDER
 SEPARATE PERMIT, TO DATE NO PERMIT HAS BEEN APPLIED
 FOR. NOTE # 12 INDICATES THE EGRESS WINDOWS ARE LOCATED
 AS SHOWN PER FBC-R 310. THIS IS A 3 DWELLING UNIT
 BUILDING AND DOES NOT FALL UNDER THE 1 & 2 FAMILY
 RESIDENTIAL CODE. THIS BUILDING FALLS UNDER THE 2017
 FBC-B.
  
 2B) NOTE # 12 INDICATES THE EGRESS WINDOWS ARE LOCATED
 AS SHOWN PER FBC-R 310, PLEASE UPDATE PLAN NOTE FOR
 EGRESS WINDOWS MUST MEET THE REQUIREMENTS OF THE 2017
 FBC-B SECTION 1030 EMERGENCY ESCAPE AND RESCUE OPENINGS
 IN R-2 OCCUPANCIES.
 1030.2 MINIMUM SIZE
 1030.2.1 MINIMUM DIMENSIONS.
 1030.3 MAXIMUM HEIGHT FROM FLOOR.
 1030.4 OPERATIONAL CONSTRAINTS.
  
 2C) NOTE # 12 INDICATES THE EGRESS WINDOWS ARE TO BE
 SHOWN ON THE PLANS, THE EGRESS WINDOWS ARE NOT SHOWN.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 2D) THERE IS A DETAIL FOR CBS WALL INFILL WITH WOOD
 FRAMING, 5/8 INCH PLYWOOD AND WIRE LATH AND STUCCO. THE
 FLOOR PLAN DOES NOT INDICATE WHERE THIS DETAIL IS TO BE
 USED. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 2E) THERE IS A DETAIL FOR CBS WALL INFILL WITH WOOD
 FRAMING, 5/8 INCH PLYWOOD AND WIRE LATH AND STUCCO.
 THE DETAIL IS LACKING COMPLIANCE WITH 2017 FBC-B 2510.6
 WATER-RESISTIVE BARRIERS. WATER-RESISTIVE BARRIERS
 SHALL BE INSTALLED AS REQUIRED IN SECTION 1404.2 AND,
 WHERE APPLIED OVER WOOD-BASED SHEATHING, SHALL INCLUDE
 A WATER-RESISTIVE VAPOR-PERMEABLE BARRIER WITH A
 PERFORMANCE AT LEAST EQUIVALENT TO TWO LAYERS OF
 WATER-RESISTIVE BARRIER COMPLYING WITH ASTM E2556, TYPE
 I. THE INDIVIDUAL LAYERS SHALL BE INSTALLED
 INDEPENDENTLY SUCH THAT EACH LAYER PROVIDES A SEPARATE
 CONTINUOUS PLANE AND ANY FLASHING (INSTALLED IN
 ACCORDANCE WITH SECTION 1405.4) INTENDED TO DRAIN TO
 THE WATER-RESISTIVE BARRIER IS DIRECTED BETWEEN THE
 LAYERS.
  
 2F) THE PLAN SHOWS SEPARATION WALLS BETWEEN EACH OF THE
 DWELLING UNITS. STATED FROM THE PLAN: THE REPAIRS TO
 THE PARTY WALL MUST BE MADE WITH 5/8 INCH DRYWALL AND 3
 ? INCH BATT INSULATION.
  
 THESE WALLS WERE TO BE BUILT AS FIRE PARTITIONS, PLEASE
 PROVIDE THE WALL RATING AND ASSEMBLY FOR THIS WALL
 SYSTEM. THE 2017 FBC-B SECTION 708.3 FIRE RESISTANCE
 RATING. FIRE PARTITIONS SHALL HAVE A FIRE RESISTANCE
 RATING OF NOT LESS THAN 1 HOUR. PLEASE PROVIDE THE UL
 OR GYPSUM WALL ASSEMBLY.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER