2019-05-14 06:52:50 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. SHOW ALL ELECTRICAL WORK TO BE PERFORMED ON THE |
| SUBMITTED PLANS. A NOTE STATING "KITCHEN COUNTERTOP |
| RECEPTACLES WILL BE PER CODE" WILL NOT SUFFICE. FBC |
| 107.2.1 NEC 210.52 |
| |
| 2. KITCHEN COUNTERTOP RECEPTACLES SPACING IS NOT CODE |
| COMPLIANT.PLEASE PROVIDE CORRECTION. NEC 210.52C |
| |
| 3. PLAN PROVIDED IS A COPY. PLANS SUBMITTED MUST HAVE |
| ORIGINAL SIGNATURES ON PLAN. ELECTRICAL PLAN IS |
| REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR THE |
| DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC |
| 107.2.1, 107.3.5.1.2 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |